background image

I.B. 3A74499B

Page 6

Effective 11/97

3-2  HANDING

DO NOT USE ANY LIFTING DEVICE AS A PLAT-
FORM FOR PERFORMING MAINTENANCE, REPAIR
OR ADJUSTMENT OF THE BREAKER OR FOR
OPENING, CLOSING THE CONTACTS OR CHARG-
ING THE SPRINGS. THE BREAKER MAY SLIP OR
FALL CAUSING SEVERE PERSONAL INJURY.
ALWAYS PERFORM MAINTENANCE, REPAIR AND
ADJUSTMENTS ON A WORKBENCH CAPABLE OF
SUPPORTING THE BREAKER.

Type W-VAC breaker shipping containers are designed
to be handled either by use of a rope sling and over-
head lifting device or by a fork truck. If containers must
be skidded for any distance, it is preferable to use roller
conveyors or individual pipe rollers.

Once a breaker has been inspected for shipping dam-
age, it is best to return it to its original shipping container
until it is ready to be installed in the Metal-Clad
Switchgear.

When a breaker is ready for installation, a lifting yoke in
conjunction with an overhead lifter or portable floor lifter
can be used to move a breaker. In some instances, this
is preferable to rolling the breaker on the floor using self
contained wheels on the cradle or carriage. If the break-
er is to be lifted, position the lifting yoke over the break-
er and insert lifters into the breaker side openings with
the lifting hole toward the interrupters. Once the lifting
yoke is securely seated in the lifting holes, the breaker
can be carefully lifted and moved.

3-3  STORAGE

If the circuit breaker is to be placed in storage, maxi-
mum protection can be obtained by keeping it in the
original container.

Before placing it in storage, checks should be made to
make sure that the breaker is free from shipping dam-
age and is in satisfactory operating condition.

The breaker is shipped with its contacts open and clos-
ing springs discharged. The indicator on the front panel
should confirm this. Insert the maintenance tool in the
manual charge socket opening (Figures 3-2 and 4-1a).
Charge the closing springs by pumping the handle up
and down about 38 times until a crisp metallic "click" is
heard. This indicates that the closing springs are
charged and is shown by the closing spring "charged"
(yellow) indicator. Remove the maintenance tool. Push
the "manual close"button. The breaker will close as
shown by the breaker contacts "closed" indicator. Push
the "manual trip" button. The breaker  will trip as shown
by the breaker contacts "open" indicator. After complet-
ing this initial check, leave the closing springs "dis-
charged" and breaker contacts "open"
(Figures 3-2, 4-1c and d).

Outdoor storage is NOT recommended. If unavoidable,
the outdoor location must be well drained and a tempo-
rary shelter from sun, rain, snow, corrosive fumes, dust,
dirt falling objects and excessive moisture must be pro-
vided. Containers should be arranged to permit free cir-
culation of air on all sides and temporary heaters should
be used to minimize condensation. Moisture can cause
rusting of metal parts and  deterioration of high voltage
insulation. A heat level of approximately 400 watts for
each 3 cubic meters of volume is recommended with the
heaters distributed uniformly throughout the structure
near the floor.

Indoor storage should be in a building with sufficient
heat and circulation to prevent condensation. If the
building is not heated, the same general rule for heat as
for outdoor storage should be applied.

!

WARNING

Содержание 36W-VAC25

Страница 1: ...1993 Cutler Hammer Instructions for Installation Operation and Maintenance of Type W VAC Vacuum Circuit Breakers W VAC Breaker Element W VAC Breaker with Carriage Assembly for SIngle Tier Switchgear W...

Страница 2: ......

Страница 3: ...LD BE ATTEMPTED ONLY BY QUALIFIED PERSONNEL THIS INSTRUCTION BOOK SHOULD NOT BE CON SIDERED ALL INCLUSIVE REGARDING INSTALLA TION OR MAINTENANCE PROCEDURES IF FUR THER INFORMATION IS REQUIRED YOU SHOU...

Страница 4: ...t Interface Check 13 SECTION 5 DESCRIPTION AND OPERATION 5 1 Interrupter Assembly 16 5 1 1 Vacuum Interrupter 16 5 1 2 Contact Erosion Indicator 17 5 1 3 T Cutout Loading Spring Indicator 17 5 1 4 Con...

Страница 5: ...Warning 25 6 2 Frequency 25 6 3 Inspection and Maintenance Procedures 26 6 4 Vacuum Interrupter Integrity Test 27 6 5 Contact Erosion and Wipe 27 6 6 Insulation 28 6 7 Insulation Integrity Check 28 6...

Страница 6: ...reaker Manual Operation Single Tier Breaker Shown 13 5 1 Flush Mounted Configuration 16 5 2 Behind the Door Configuration 17 5 3 Closeup of Type W VAC Breaker Vacuum Interrupters and Current Carrying...

Страница 7: ...W VAC BREAKERS ARE PROTECTIVE DEVICES AS SUCH THEY ARE MAXIMUM RATED DEVICES THEREFORE THEY SHOULD NOT UNDER ANY CIRCUMSTANCES BE APPLIED OUT SIDE THEIR NAMEPLATE RATINGS WARNING Table 1 1 Type W VAC...

Страница 8: ...he hf 3L h3Le he hf S hS L h W he Y h Y J h U he hf H h V he hf he N he hf 3 hf J he W he V4 L h U he hf N h V he3L hf H h S hf J he W he Y L h U hf N h V he hf H h hf L h X he X hf J h N1 heV H h N...

Страница 9: ...V M 5 7 V H e hf 3L e N V h Xg X h X X h V h V e N1 hS N1 h L Lh7H h X f31 X T5 Xe Xe J5 Xe X h he X e e e e fS5 V Y V eV g U hf e f g f V f V hJ 1 h N1 h H f Y V h7 h J h h 3L f hf h Lhe S J h3 V h 7...

Страница 10: ...not work on a breaker with the secondary test cou pler engaged Failure to disconnect the test coupler could result in an electrical shock leading to death per sonal injury or property damage Do not wo...

Страница 11: ...for any signs of damage or rough handing Open the con tainer carefully to avoid any damage to the contents When opening the container be careful that any loose items or hardware are not discarded with...

Страница 12: ...cks should be made to make sure that the breaker is free from shipping dam age and is in satisfactory operating condition The breaker is shipped with its contacts open and clos ing springs discharged...

Страница 13: ...97 Figure 3 2 Type W VAC breaker element faceplate 1 2 3 8 7 4 5 6 Front Panel Manual Charge Socket Open Closed Indicator Spring Charged Discharged Indicator Operation Counter Rating Nameplate Manual...

Страница 14: ...1 2 3 4 5 L H Closing Spring Anti pump Relay Auxiliary Switch Motor Cutoff Switch Closing Cam Spring Release Close Coil Assembly Shunt Trip Assembly Position Switch Charging Motor Charging Pawl Ratch...

Страница 15: ...4 Rear external view of W VAC breaker element 1 Secondary Disconnect Lifter Yoke Opening Support Insulator Primary Disconnect Vacuum Interrupter Contact Loading Spring Wipe Spring Operating Rod Drive...

Страница 16: ...view W VAC breaker with carriage assembly for single tier switchgear Side View Rear View Mechanism Enclosure Support Insulator Primary Disconnect Levering in Screw Carriage Carriage Wheel Shoot Bolt...

Страница 17: ...VAC breaker with cradle assembly for double tier switchgear Front View Rear View Mechanism Enclosure Support Insulator Primary Disconnect Levering in Screw Cradle Cradle Wheel Shutter Operator Leveri...

Страница 18: ...TACT EROSION AND WIPE Manually charge the closing springs and close the breaker Check contact erosion and wipe as described in Section 6 5 4 6 PRIMARY CIRCUIT RESISTANCE Check the primary circuit resi...

Страница 19: ...Type W VAC breaker manual operation single tier breaker shown a Inserting the maintenance tool into the manual charging socket b Lifting shoot lever permits insertion of levering crank c Manually clos...

Страница 20: ...Anti Close Interlock This interlock prevents releasing the closing springs electrically or manually if the breaker is already closed d Anti Latch Interlock This interlock prevents the breaker from bei...

Страница 21: ...sembly version lift the shoot bolt lever and pull the breaker out The breaker will close and trip as it comes out from the Test position 2 For the double tier configuration cradle assembly version ret...

Страница 22: ...is racked into the fully connected position Possibility 3 The basic breaker element combined with a cradle assembly is used for double tier switchgear This combination is only for use in a behind the...

Страница 23: ...is located on the moving stem of the interrupter Figures 6 2 and 6 3 In order to determine if the contacts have eroded to the extent that the interrupter must be replaced close the breaker and observ...

Страница 24: ...ed to the support molding resulting in the support molding being enclosed on all four vertical sides Figure 5 4 5 2 STORED ENERGY MECHANISM KEEP HANDS AND FINGERS AWAY FROM THE BREAKER S INTERNAL PART...

Страница 25: ...gh the main link to close the breaker In Figure 5 5c the linkage is shown with the breaker in the closed position before the closing springs have been recharged Interference of the trip D shaft with t...

Страница 26: ...T XV X W T h V XV T R Ug N L N R XV U N1g W 3L X V S X Y V I 3 eW R h eV4 UeW g W XfV 7H 0R T T KS5 g 0R R40Y e 6T e W eI Y O g W Yh 0Y 7H hfV L g 3L f Kh V X S 3 O e eV X f he Y e V40Y h3Le S e f e h...

Страница 27: ...e V h g f e e V e e g hf f e e e e f W hf e f Y e e f J5 W2 Y h Xe f fW2 e U heV Me V e hf f g f W g W hO U he f Y f 0Y V g T e f f e eV U O K W V g 0R4 e f Y J5 Y X X V X e f f g J LV f X S Xh e e T...

Страница 28: ...nted male plugs To disengage the sec ondary plugs from the TEST position simply push the carriage to the rear 5 3 3 UNDERVOLTAGE TRIP DEVICE The undervoltage trip device for W VAC breakers is an elect...

Страница 29: ...d by the breaker operating shaft prevents the levering crank from being inserted with the breaker in the Closed position 5 4 3 ANTI CLOSE INTERLOCK This interlock prevents releasing the closing spring...

Страница 30: ...6Xg gW 6K f e W 1 6K f gW2 6Kg g O2 6X W2 6Kg f W2 X W26Kg Lg O2 6X gO2 6X N N X W 6K H 3 X J L W2 5 W2 6X 7 W2 W26X 3 K e f O 5 X f f W H 6X eJ eW 5 6X e Lf O f f O2 1 7 6Xf fW 1 7 6XfJ 1f W2 1 W2 6X...

Страница 31: ...he g V he 3T5 f Y eS 0 Me Hhe X 3T Xh N H g W 7UfV U O he h V e W V X g g U V U he U N R g 3L g N1 S he h X e V h N1 g U he g S g g S1 he Y e W g he h 7H g f 3Lhe g f h 3L hf eV he h 3L X V hf 3T X he...

Страница 32: ...7H 7 L heS5 75 7H V f 3 h X he f N1 e R4 g S S g He hV g O he X f gV g 7H e 5 X e S S g g L e V X U he fO2 f X V h 3L 3Lg he Ke X f e e7He U g W e f h U he S f h f e V Xe 7H 7 heW e 31 1 Le N1 heN1 31...

Страница 33: ...free cloth Primary Disconnects No burning or damage Visual Check Replace if burned damaged or eroded 3 Control Closing and Tripping Device Smooth and correct Test closing and tripping Replace any defe...

Страница 34: ...uld have sufficient volt ampere capacity It is recommended that the equipment be capable of delivering 25 milliamperes for one minute Although an ac high potential test is recommended a dc test may be...

Страница 35: ...55812CA or commercial equivalent Secondary control wiring requires inspection for tightness of all connections and damage to insulation 6 7 INSULATION INTEGRITY CHECK Primary Circuit The integrity of...

Страница 36: ...c These bearings are packed at the factory with a top grade slow oxidizing grease which normally should be effective for many years They should not be disturbed unless there is definite evidence of sl...

Страница 37: ...ood grease solvent Don not use carbon tetracholride They should then be washed in light machine oil until the cleaner is removed After the oil has been drawn off the bearings should be packed with Cut...

Страница 38: ...itch off Secondary Disconnects Motor Cut off Switch Poor or burned contacts Lever not operational Terminals and connectors Poor or burned contacts Motor Brushes worn or commutator segment open Mechani...

Страница 39: ...ch or trip bar not reset Auxiliary Switch b contact open or burned Motor Cut off Contacts open or burned Trip Coil Assembly Clapper fails to reset Pole Shaft Not open fully Trip Latch Reset Spring Dam...

Страница 40: ...en Terminals and Connections Poor or burned or open Trip Mechanism Trip Clapper Jammed Trip Bar Trip Latch Jammed Trip Sound Trip Mechanism Pole Shaft Jammed Operating Rod Assembly Broken or pins out...

Страница 41: ...and con tinuity requirements Each customer should develop his own stock level based on operating experience Refer to Table 7 1 for guidance 7 2 ORDERING INSTRUCTIONS a Always specify the breaker rati...

Страница 42: ...W M I MI Y hg Y X hf h 31 hf g V hf 3 6T KO2 W26Xhe S 40R4 U 0R X h 6T T W Yf B 9e h X S U 7U T K C MB hf V4 0R R N U H f g U S 6T T2 h J R MI R R he Y V Yh g h hf h hf h hf h hf h hf h h h e f h M h...

Страница 43: ...125 VAC Cap trip 3759A76G02 1 220 250 VDC 220 250 VAC Cap trip 3759A76G03 1 15 UV Trip Coils 48 VDC 8067A19G01 1 110 125 VDC 8067A19G02 1 220 250 VDC 8067A19G03 1 16 Motor Cut Off Switch 5677B02G01 1...

Страница 44: ...ard 691C662G01 1 UV 691C666G01 1 21 Trip Latch Hatchet 699B040G01 1 22 Cluster Assembly 630A 699B104G01 1 800 1250A 508B022G01 1 1600 2000A 5677B328G01 1 23 Shock Absorber 5677B26H01 1 W f hf e h 6K W...

Страница 45: ...I B 3A74499B Page 39 Effective 11 97...

Страница 46: ...I B 3A74499B Page 40 Effective 11 97...

Страница 47: ...I B 3A74499B Page 41 Effective 11 97...

Страница 48: ...e contract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF...

Отзывы: