Fault codes and troubleshooting
Eaton 1250W / 1500W / 1800W Inverter Operation and Installation Guide
IM SP180164 / Rev D www.eaton.com
Fault codes and troubleshooting
Inverter Section
Table 3. DC Input Warning and Shutdown
•
Unit start up voltage (Lo setting): > 10.5 +/- 0.3 VDC and < 16.0 +/- 0.3 VDC
•
Unit start up voltage (Mid setting): > 11.8 +/- 0.3 VDC and < 16.0+/- 0.3 VDC
•
Unit start up voltage (Hi Setting): > 12.2 +/- 0.1 VDC and < 16.0 +/- 0.3 VDC
ote:
N
1.
Unit will shut down instantly and restart automatically if voltage returns to less than 15.5V within 30 seconds
2.
If DC voltage is not less than 15.5V within 30 seconds, unit will require manual reset by power button
3.
Unit will shut off instantly if DC voltage drops below 10V regardless of settings
4.
Unit will shut off if DC voltage is below shutdown for 10 seconds
5.
Unit will shut off if DC voltage is below shutdown for 90 seconds
6.
Unit will shut off if DC voltage is below shutdown for 2 minutes
Table 4. AC output overload protection and warning shutdown
Model
Condition
Display
Audible alarm
Power (W)
12-110-1800-xx
Warning (+/- 100W)
2000
E06
Beep @ 0.33Hz
Shutdown (+/- 100W)
2100
E03
Beep @ 1Hz
12-110-1500-xx
Warning (+/- 100W)
1700
E06
Beep @ 0.33Hz
Shutdown (+/- 100W)
1800
E03
Beep @ 1Hz
12-110-1250-xx
Warning (+/- 100W)
1450
E06
Beep @ 0.33Hz
Shutdown (+/- 100W)
1550
E03
Beep @ 1Hz
AC output short circuit protection
A short circuit may be applied to the AC output continuously during inverter mode without damage to any components. Unit
will shut down within 10 seconds, and display will indicate ‘E03’ with the buzzer beeping @ 1 Hz.
ote:
N
Manual reset is required to restart Inverter after AC Overload or Short Circuit shutdown. System will automatically
reset AC Overload or Short Circuit shutdown error when utility is available. The supplemental protector or the branch
protection specified in the Installation Guide should be open under bypass short circuit output condition.
Condition
Disconnect
setting
Setting
(+/- 0.3V)
Recovery
(+/- 0.3V)
Display
Audible Alarm
Comment
Over voltage instant shutdown
Lo, mid or hi
16.0
15.5
E02
Beep @ 1Hz
Notes 1, 2
Under voltage instant shutdown
Lo, mid or hi
10.0
--
--
--
Note 3
Under voltage shutdown
Lo
10.5
12.0
E01
Beep @ 1Hz
Note 4
Under voltage warning
Lo
11.0
11.3
E05
Beep @ 0.33Hz
--
Under voltage shutdown
Mid
11.8
12.3
E01
Beep @ 1Hz
Note 5
Under voltage warning
Mid
11.8
12.1
E05
Beep @ 0.33Hz
--
Under voltage shutdown
Hi
12.2
12.7
E01
Beep @ 1Hz
Note 6
Under voltage warning
Hi
12.2
12.5
E05
Beep @ 0.33Hz
--