17
Choose a location for inverter mounting
Eaton 1250W / 1500W / 1800W Inverter Operation and Installation Guide
IM SP180164 / Rev D www.eaton.com
Ground Fault Circuit Interrupters (GFCIs) –
In the case where the current to ground exceeds specified value, a GFCI
device will de-energize the circuit. This protects from electric shock and is usually required for wet/damp locations.
Choose a location for inverter mounting
WARNING
Fire and explosion hazard -
It is possible for the inverter to produce arcs and/or sparks, do not install or use inverter near
flammable materials (i.e. gas-powered machines, fuel tanks, or any components connecting to a fuel supply). Follow any
instructions from the battery manufacturer being used.
WARNING
Fire hazard -
Ensure the ventilation openings are not covered or obstructed to reduce risk of fire. Installing the inverter in a
compact compartment will be detrimental and may result in overheating.
IMPORTANT
Location(s) must conform to these required parameters:
•
Dry
: Do not allow water or other fluids to splash or drip on to the inverter.
•
Cool
: Ambient, air temperature should be between 0°C and 50°C (32°F and 122°F). Power linearly derates from 100%
at 25°C to 70% at 50°C.
•
Ventilated
: Provide a minimum of 5 inches (13cm) of clearance at the DC end of inverter for air flow. Also give at least 1
inch (2.5cm) on each side, and 2 inches (5cm) at the AC end. Do not allow ventilation to be obstructed.
•
Safe
: Do not install the inverter in the same compartment as flammable liquids, batteries, or any unsafe materials.
•
Close-in
: Avoid excessive cable lengths, especially between inverter and battery banks.
•
Batteries
: Never allow battery acid to come in contact with the inverter or the wiring to and from the devices. It is also
important to be aware of the corrosive gases that may be coming into contact with the inverter.