13 Technical data
ESR5-NV3-30
12/19 MN049010EN
www.eaton.com
27
General data
Relay type
Electromechanically forcibly guided, dust-proof relay
Nominal operating mode
100 % operating factor
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Mounting position
any
Air and creepage distances between the power circuits
DIN EN 60947-1
Rated surge voltage / insulation
4 kV (basic insulation)
Dimensions
W x H x D
22.5 x 99 x 114.5 mm
Connection data
Conductor cross section, solid
0.2 mm
2
- 2.5 mm
2
Conductor cross section, stranded
0.2 mm
2
- 2.5 mm
2
Conductor cross section AWG/kcmil
24
- 12
Stripping length
7 mm
Ambient conditions
Ambient temperature (operation)
-20 °C - 45 °C
Ambient temperature (storage/transport)
-40 °C - 70 °C
Max. permissible relative humidity (operation)
75 %
Max. permissible humidity (storage/transport)
75 %
Certification / Approvals
Approvals
Safety data
Stop category according to IEC 60204-1
0, 1