RM-208 CB.13.01 Easy Line Documentation  

RDN 10000795 

7

 

20.03.2019 

 

5   “Step by step” settings 

5.1   Function when shipped 

The down time cleaning input 10, 11 is bridged at the factory. Once the supply voltage is at RM-208 CB, 

the solenoid valves are controlled consecutively in sequence.  The filter control system automatically 

detects how many valves are connected. 
For connecting an external 

p switch, see section 6.3 “Cleaning via start / stop input (external 

p switch)”. 

To activate the down time cleaning, see section 6.2 “Down time cleaning”. 
If another function is required or if additional functions are to be activated, the parameter setting of the 

RM-208 CB must be changed. See also section 5.2. 
 

 

 

5.2   Setting parameters 

 

To set or check the parameters, proceed as follows: 

 

 

Use the parameter list in section 5.3 to search for the parameters you want to change or check. 

On the RM-208 CB, press buttons 

  and 

  simultaneously, for at least 3 seconds. The 

program then changes from operation mode to parameter selection mode. The parameter P01 

“Pulse time” is displayed on the text display at its set value. 

 

 

Press the 

button to call up all following parameters P02 ... P11 in sequence. The parameters 

already displayed can be accessed by repeatedly pressing the 

 button. 

 

 

To change the value of a displayed parameter, press the ENTER button for at least one 

second. The program then changes from parameter selection mode to parameter setting mode. 

 

 

Press the 

  button to increase the parameter value displayed in increments. Press the 

 

button to decrease the parameter value displayed. 

 

 

Press the ENTER button for at least 3 seconds. The new parameter value is stored. The text 

display will briefly display the message “

Store

”. The program automatically returns to the 

parameter selection mode. You can now call up other parameters and check or change their 

values. 

 

 

So that the program changes from parameter selection mode to operation mode, press buttons 

 and 

 simultaneously for at least 3 seconds. 

 

If the program is still in parameter setting mode, follow the instructions given under point 

 

 

 

 

The symbols shown on the right will be shown in the 

lower left-hand corner of the text display. They 

indicate to the operator which mode the equipment is 

currently in. 

 

+ -  

Operation mode 

+^-  

Parameter selection mode 

+>-  

Parameter setting mode 

 

 

 

If no buttons are pressed for 4 minutes, the RM-208 CB automatically returns from parameter 

selection mode or parameter setting mode to operation mode with the last values stored. 

Содержание RM-208 CB.13.01

Страница 1: ...Operating and Installation Instructions Filter control system RM 208 CB 13 01 EasyLine Supply voltage 110 V AC...

Страница 2: ...structions for the replacement of the device fuse 11 7 2 Cleaning the controller 12 7 3 Manufacturing 12 8 Text messages on the display 13 9 Details on the equipment function 14 10 Glossary 15 11 Tech...

Страница 3: ...cable laws conditions orders and regulations governing the setting up of electrical equipment must be observed with respect to the installation site Setting of equipment with degree of protection IP00...

Страница 4: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 4 20 03 2019 3 Assembly Wall mounting of the filter controls is not permitted The device may only be mounted to machine parts...

Страница 5: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 5 20 03 2019 4 Step by step installation Supply voltage connection Solenoid valve connection Connection of expansion modules RM LV8 RM LV16...

Страница 6: ...accessible for the user and to be marked as disconnecting device for the equipment The wires and cables used for the connection of the controls must be suitable for an ambient temperature of up to 13...

Страница 7: ...ameters P02 P11 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one seco...

Страница 8: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 8 20 03 2019...

Страница 9: ...ve test 2 Input test 3 5 For manufacturer purposes only Off 0 0 5 P09 P09 Ser run hour Service operating hours P10 P10 Ser run h AL Service operating hours alarm 0 h 0 25000 h P11 P11 Ser r h Code Ser...

Страница 10: ...e down time cleaning perform the following steps Remove the factory fitted wire jumper on input 10 11 Connect a free auxiliary contact make contact of the fan contactor to terminals 10 and 11 The inpu...

Страница 11: ...the fan control Activate signal to input 10 11 Cleaning ineffective Interval time too long Set parameter P02 Interval to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter...

Страница 12: ...part of the housing and tighten the six screws evenly Switch on the supply voltage again 7 2 Cleaning the controller Wipe only with a damp cloth if outside of device is soiled 7 3 Manufacturing The f...

Страница 13: ...abled via input 10 11 and stopped via input 12 13 Cleaning Off Val No The control has been enabled via input 10 11 and started via input 12 13 Cleaning On Val No Down time cleaning active DTC Cleaning...

Страница 14: ...Relay output 8 9 to control extractor elements If automatic components for dust removal extractor elements are fitted these need to be in operation during cleaning and during down time cleaning Connec...

Страница 15: ...r element contactor Contactor which switches an extractor element drive unit on and off I O module Input output module module for the input and output of control signals Operation mode Status of the R...

Страница 16: ...ell 5MT 300 mA ESKA UL 521 012 Temperature range 20 C to 50 C Protection class Housing IP 66 not evaluated by UL Type 5 Installation torque of cover screws 1 5 Nm Weight approx 0 8 kg Installation hei...

Отзывы: