RM-208 CB.13.01 Easy Line Documentation  

RDN 10000795 

9

 

20.03.2019 

5.3   Parameter list 

 

Pa

ra

m

. n

o.

 

Text on the display  Explanation 

Factory settings  Setting range 

P01 

P01 Pulse time   

Pulse time 

60 ms 

15 ... 2500 ms 

P02 

P02  Interval    

Pause time 

10 s 

1 ... 500 s 

P03 

P03 DT interval  

Down time interval time 

6 s 

1 ...100 s 

P04 

P04 tot Valve no 

Total no. of valves* 

0 ... 128 

P05 

P05 DT cycles    

Down time cleaning cycles 

0, 2 ... 32 

P06 

P06 Operating h  

Operating hours 

– 

0 ... 250000 h 

P07 

P07   Language   

Language for the display text 

D, GB, F, I, NL, 

DK, FIN, PL, E 

P08 

P08 Test Mode    

0    =  Test mode off 

1    =  Valve test 

2    =  Input test 

3-5  =  For manufacturer  

      purposes only 

Off (0) 

0 ... 5 

P09 

P09 Ser.run hour 

Service operating hours 

– 

– 

P10 

P10 Ser.run h.AL 

Service operating hours alarm 

0 h** 

0 ... 25000 h** 

P11 

P11 Ser.r.h.Code 

Service operating hours code 

0 ... 250 

 

 

*

  Number of all valves connected to the RM-208 CB and to the expansion modules. The parameter is used by the equipment for 

internal monitoring purposes and need only be set, if expansion modules are fitted.  If the equipment detects that the total 

number of valves set is different from the actual number of valves controlled, an alarm message is issued. 

 

**

 If the parameter is set to the value 0 h, the alarm is switched off. 

 

 

 

 

 

The parameters P09 and P10 are only displayed if the service operating hours code (parameter 

P11) has been entered. 

Содержание RM-208 CB.13.01

Страница 1: ...Operating and Installation Instructions Filter control system RM 208 CB 13 01 EasyLine Supply voltage 110 V AC...

Страница 2: ...structions for the replacement of the device fuse 11 7 2 Cleaning the controller 12 7 3 Manufacturing 12 8 Text messages on the display 13 9 Details on the equipment function 14 10 Glossary 15 11 Tech...

Страница 3: ...cable laws conditions orders and regulations governing the setting up of electrical equipment must be observed with respect to the installation site Setting of equipment with degree of protection IP00...

Страница 4: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 4 20 03 2019 3 Assembly Wall mounting of the filter controls is not permitted The device may only be mounted to machine parts...

Страница 5: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 5 20 03 2019 4 Step by step installation Supply voltage connection Solenoid valve connection Connection of expansion modules RM LV8 RM LV16...

Страница 6: ...accessible for the user and to be marked as disconnecting device for the equipment The wires and cables used for the connection of the controls must be suitable for an ambient temperature of up to 13...

Страница 7: ...ameters P02 P11 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one seco...

Страница 8: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 8 20 03 2019...

Страница 9: ...ve test 2 Input test 3 5 For manufacturer purposes only Off 0 0 5 P09 P09 Ser run hour Service operating hours P10 P10 Ser run h AL Service operating hours alarm 0 h 0 25000 h P11 P11 Ser r h Code Ser...

Страница 10: ...e down time cleaning perform the following steps Remove the factory fitted wire jumper on input 10 11 Connect a free auxiliary contact make contact of the fan contactor to terminals 10 and 11 The inpu...

Страница 11: ...the fan control Activate signal to input 10 11 Cleaning ineffective Interval time too long Set parameter P02 Interval to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter...

Страница 12: ...part of the housing and tighten the six screws evenly Switch on the supply voltage again 7 2 Cleaning the controller Wipe only with a damp cloth if outside of device is soiled 7 3 Manufacturing The f...

Страница 13: ...abled via input 10 11 and stopped via input 12 13 Cleaning Off Val No The control has been enabled via input 10 11 and started via input 12 13 Cleaning On Val No Down time cleaning active DTC Cleaning...

Страница 14: ...Relay output 8 9 to control extractor elements If automatic components for dust removal extractor elements are fitted these need to be in operation during cleaning and during down time cleaning Connec...

Страница 15: ...r element contactor Contactor which switches an extractor element drive unit on and off I O module Input output module module for the input and output of control signals Operation mode Status of the R...

Страница 16: ...ell 5MT 300 mA ESKA UL 521 012 Temperature range 20 C to 50 C Protection class Housing IP 66 not evaluated by UL Type 5 Installation torque of cover screws 1 5 Nm Weight approx 0 8 kg Installation hei...

Отзывы: