3
Keep pressing
for 3 second, the current selection
will flash, use
and
to change the Baud rate.
Options: 1.2k, 2.4k,4.8k,9.6k ( default ),19.2k
Keep press
for 3s to confirm the selection.
4
Keep pressing
for 3 second, the current selection
will flash, use
and
to change the Parity.
Options: EVEN,ODD,NONE ( default )
5
Keep pressing
for 3 second, the current selection
will flash, use
and
to change the type of
Pulse Output.
Options: total kWh, IMP kWh, EXP kWh
6
Keep pressing
for 3 second, the current selection
will flash, use
and
to change the pulse
constant.
Options: 1000, 100, 10, 1 imp/kWh
*Default pulse constant is related to the CT1 setting
7
Keep pressing
for 3 second, the current selection
will flash, use
and
to change the pulse
width.
Options: 60, 100, 200, unit: ms