PART 3

 

Modbus Protocol

   

 

Input registers are used to indicate the present values of the measured and calculated electrical quantities. 
Each parameter is held in two consecutive16 bit register. The following table details the 3X register address, 
and the values of the address bytes within the message. A (*) in the column indicates that the parameter 
is valid for the particular wiring system. Any parameter with a cross(X) will return the value zero. Each 
parameter is held in the 3X registers. Modbus Protocol function code 04 is used to access all parameters. 
For example, to request:        Amps 1        Start address=0006 
                                                                          No. of registers =0002 
                                                    Amps 2        Start address=0008 
                                                                          No. of registers=0002 

Each request for data must be restricted to 40 parameters or less. Exceeding the 40 parameter limit will cause 

a Modbus Protocol exception code to be returned. 

 

 

 

Address 

(Register

)

 

            DCM230 Input Register 

Parameter           

 

   

Modbus 

  Protocol Start 

    Address Hex

 

            Description

 

Length 
(bytes) 

Data 

Format 

Units

 

Hi 

Byte

 

Lo 

Byte

 

30001

 

Line to neutral volts.

 

4

 

Float

 

V

 

00

 

00

 

30007

 

Current.

 

4

 

Float

 

A

 

00

 

06

 

30013

 

Active power.

 

4

 

Float

 

W

 

00

 

0C

 

30073

 

Import active energy

 

4

 

Float

 

kWh

 

00

 

48

 

30075

 

Export active energy 

4

 

Float

 

kWh

 

00

 

4A

 

30085

 

Total system power demand 

4

 

Float

 

W

 

00

 

54

 

30087

 

Maximum total system power demand 

4

 

Float

 

00

 

56

 

30343

 

Total active energy

 

4

 

Float

 

kWh

 

01

 

56

 

30385

 

Resettable partial kWh

 

4

 

Float

 

kWh 

01

 

80

 

34877

 

Total active Energy Rate 1

 

Float

 

kWh 

13

 

0C

 

34879

 

Total active Energy Rate 2

 

Float

 

kWh 

13

 

0E

 

34881

 

Total active Energy Rate 3

 

Float

 

kWh 

13

 

10

 

34883

 

Total active Energy Rate 4

 

Float

 

kWh 

13

 

12

 

34885

 

Import active Energy Rate 1 

Float

 

kWh 

13

 

14

 

34887

 

Import active Energy Rate 2

 

Float

 

kWh 

13

 

16

 

34889

 

Import active Energy Rate3

 

Float

 

kWh 

13

 

18

 

34891

 

Import active Energy Rate 4

 

Float

 

kWh 

13

 

1A

 

34893

 

Export active Energy Rate 1

 

Float

 

kWh 

13

 

1C

 

34895

 

Export active Energy Rate 2

 

Float

 

kWh 

13

 

1E

 

34897

 

Export active Energy Rate 3

 

Float

 

kWh 

13

 

20

 

34899

 

Export active Energy Rate 4

 

Float

 

kWh 

13

 

22

 

38193

 

Total Last 1 month active Energy 

(Total

Rate1

Rate2

Rate3

Rate4)

 

20 

Float

 

kWh 

 

20

 

00

 

Содержание DCM230

Страница 1: ...73 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 1 Measures kWh W V A etc Bi directional measurement IMP EXP Pulse output RS485 Modbus Din rail mounting 35mm DC shunt connection Class 1 DCM230 DC Energy Meter User Manual V1 5 2019 ...

Страница 2: ...dbus RTU The meter has two versions working with AC or DC power supply Input voltage range up to 300 600 1000V DC and current inputs are flexible with DC shunt and current sensors The multi tariff version has a RTC equipped inside it can provides multi tariff information and monthly records PART 1 Specification Model list General Specifications Voltage DC Input 5 300V DC 5 600V DC 5 1000V DC Auxil...

Страница 3: ...ry input Primary current range 0 2000A Second input 75mV in default 45mV 60mV optional RS485 Output for Modbus RTU For Modbus RTU the following RS485 communication parameters can be configured from the Set up menu Baud rate 1200 2400 4800 9600 19200 bps Parity none default odd even Stop bits 1 or 2 RS485 network address nnn 3 digit number 001 to 247 Modbus Word order Hi Lo byte order is set automa...

Страница 4: ...er value will be changed The user can read this register through communication to determine whether an overcurrent alarm has occurred The pulse outputs can be set to generate pulses to represent Import kWh Export kWh total kWh The pulse output is passive type complies with IEC62053 31 Class A Environment Operating temperature 25 to 70 Reference temperature 23 2 Relative humidity 0 to 90 non conden...

Страница 5: ...nic Co Ltd Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 5 Full Screen stay 2s Software Version stay 2s Current Modbus address stay 2s ...

Страница 6: ... stay 2s Total active energy kWh Total Import Export Max read 999999 9 kWh Buttons function There are two buttons on the front panel Scroll the display for data checking Changing option at Set up mode Exit the Set up mode Set up mode entry Confirmation After initialization and self checking program the meter displays the measured values The default page is total kWh If the user wants to check othe...

Страница 7: ...Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 7 Total active energy kWh Total Import Export Display format 5 2 6 1 5 2 99999 99 100000 0 999999 9 00000 00 Partial resettable active energy Display format 5 2 6 1 5 2 99999 99 100000 0 999999 9 00000 00 T1 T4 total kWh Multi tariff version only Voltage ...

Страница 8: ... 83698881 83698882 Fax 0086 573 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 8 Current Power Display format 1000 W XXX W 1000kW XXX XXX kW For other value XXXX XX kW Pulse constant CT1 Primary current ...

Страница 9: ...Electronic Co Ltd Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 9 Meter address Baud rate Parity Date Multi tariff version only ...

Страница 10: ...e Multi tariff version only Software Version Set up Mode To get into Set up Mode the user need press the Enter button for 3 second Page Display Descriptions 1 Password To get into Set up mode it asks a password confirmation Default password 1000 Use and to enter correct password 2 Keep pressing for 3 second the current selection will flash use and to change the Modbus address Options 1 247 Keep pr...

Страница 11: ... confirm the selection 4 Keep pressing for 3 second the current selection will flash use and to change the Parity Options EVEN ODD NONE default 5 Keep pressing for 3 second the current selection will flash use and to change the type of Pulse Output Options total kWh IMP kWh EXP kWh 6 Keep pressing for 3 second the current selection will flash use and to change the pulse constant Options 1000 100 1...

Страница 12: ...t transformer the CT1 shall be 0100 Keep press for 3s to confirm the selection Deafult 1A 9 Keep pressing for 3 second the current selection will flash use and to change the DIT Demand Integration Time Options 0 5 8 10 15 20 30 60 default 10 Use to select the scroll display time option Keep pressing for 3 second the current selection will flash use and to enter the options 0 60s Default 0 s repres...

Страница 13: ...he new password The range is from 0001 to 9999 Default 1000 13 Shunt wiring Use to select the shunt connection option Keep pressing for 3 second the current selection will flash use to choose the connection way Option N P N Negative type default P Positive type 14 Use to select the date interface Keep pressing for 3 second Multi tariff version only 14 1 the current selection will flash use and to ...

Страница 14: ...strongroup com 14 15 1 the current selection will flash use and to set the correct time information Multi tariff version only 16 Tariff information for view only and cannot be set Multi tariff version only 16 1 T1 means tariff number Range from T1 T4 T0 means invalid rate number 01 means serial number Range 01 08 18 00 mean the starting time of current tariff number Keep pressing button to exit th...

Страница 15: ...83698881 83698882 Fax 0086 573 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email sales eastrongroup com 15 Wiring diagram Terminal Connection AC Power Supply DC Power Supply Shunt Connection Positive Type Negative Type Dimensions ...

Страница 16: ...urned Address Register DCM230 Input Register Parameter Modbus Protocol Start Address Hex Description Length bytes Data Format Units Hi Byte Lo Byte 30001 Line to neutral volts 4 Float V 00 00 30007 Current 4 Float A 00 06 30013 Active power 4 Float W 00 0C 30073 Import active energy 4 Float kWh 00 48 30075 Export active energy 4 Float kWh 00 4A 30085 Total system power demand 4 Float W 00 54 30087...

Страница 17: ...h 20 64 38303 Total Last 12 month active Energy Total Rate1 Rate2 Rate3 Rate4 20 Float kWh 20 6E 312289 Total Last 1 day active Energy 4 Float kWh 30 00 312291 Total Last 2 days active Energy 4 Float kWh 30 02 312293 Total Last 3 days active Energy 4 Float kWh 30 04 312295 Total Last 4 days active Energy 4 Float kWh 30 06 312297 Total Last 5 days active Energy 4 Float kWh 30 08 312299 Total Last 6...

Страница 18: ...gy 4 Float W 40 08 316395 Total system power demand 4 Float kWh 40 0A 316397 Maximum total system power demand 4 Float kWh 40 0C 316399 Total active energy 4 Float kWh 40 0E 316401 Current resettable total active energy 4 Float kWh 40 10 316403 Current overload alarm 00 00 means no alarm 00 01 means Current overload alarm 2 Hex None 40 12 Note 1 The method of power demand calculation is Import Exp...

Страница 19: ... Format Float r w 40013 Pulse Width 00 0C Write pulse1 on period in Milliseconds 60 100 or 200 default 100 Length 4 byte Data Format float r w 40019 Network Parity and Stop 00 12 Write the network port parity stop bits for MODBUS Protocol where 0 1 stop bit and none parity default 1 1 stop bit and even parity 2 1 stop bit and odd parity 3 2 stop bit and none parity Requires a restart to become eff...

Страница 20: ...Options 0 120 munites 0 means the backlit always on Default 60 Length 4byte Data Format Float r w 40087 Pulse output type 00 56 Options 1 means Import active energy 2 means total active energy 4 means Export active energy Default 2 Length 4 byte Data Format float r w 48193 Connection method of shunt 20 00 Setting on shunt connection Option 00 4E means Negative type default 00 50 means Positive typ...

Страница 21: ...2x118x22 300 A 75 60 45 mV 0 5 26x127x22 400 A 75 60 45 mV 0 5 36x127x22 500 A 75 60 45 mV 0 5 46x127x22 600 A 75 60 45 mV 0 5 55x127x22 750 A 75 60 45 mV 0 5 76x127x22 1000 A 75 60 45 mV 0 5 96x127x22 1500 A 75 60 45 mV 0 5 113x127x22 or 87x200x97 2000 A 75 60 45 mV 0 5 136x200x97 Second minute hour week date month year 20 Length 8 byte Data Format BCD 463233 Tariff information F7 00 Date definit...

Отзывы: