- 19 -
Address
Register
Parameter
Modbus
Protocol
Start Address Hex
Valid range
Mode
High Byte Low Byte
40003
Demand Period
00
02
Write demand period: 0~60 minutes, default 60.
Setting the period to 0 will cause the demand to
show the current parameter value, and demand
max to show the maximum parameter value
since last demand reset.
Length : 4 byte
Data Format : Float
r/w
40005
Slide time
00
04
Default 1, min.
Range
:
1 ~ (Demand Period -1).
Length : 4 byte
Data Format : Float
r/w
40013
Pulse Width
00
0C
Write pulse1 on period in
Milliseconds: 60, 100 or 200, default 100.
Length : 4 byte
Data Format:
float
r/w
40019
Network Parity
and Stop
00
12
Write the network port parity/stop bits for
MODBUS Protocol, where:
0 = 1 stop bit and none parity, default.
1 = 1 stop bit and even parity.
2 = 1 stop bit and odd parity.
3 = 2 stop bit and none parity. Requires a restart
to become effective.
Length : 4 byte
Data Format : Float
r/w
40021
Modbus
address
00
14
Write the Modbus address
Address: 1 to 247 for MODBUS Protocol, default
1. Requires a restart to become effective.
Length : 4 byte
Data Format : Float
r/w
40023
Pulse constant
00
16
Options
:
0 means 1000 imp/kWh
1 means 100 imp/kWh
2 means 10 imp/kWh
3 means 1 imp/kWh
Length : 4 byte
Data Format:
float
r/w
40025
Password
00
18
Write password for access to protected
registers.
Length : 4 byte
Data Format : Float
ro