~ 22 ~
EAHI-5000-SL
5-6 mm
2
EAHI-6000-SL
5-6 mm
2
PV1/PV2/PV
Input (+, -)
EAHI-3000-SL
3-4mm
2
EAHI-3600-SL
3-4mm
2
EAHI-5000-SL
3-4mm
2
EAHI-6000-SL
3-4mm
2
BAT (+, -)
EAHI-3000-SL
10-15 mm
2
EAHI-3600-SL
10-15 mm
2
EAHI-5000-SL
25-35 mm
2
EAHI-6000-SL
25-35 mm
2
Table 6.2 Recommended cable
6.1 Connection of battery end
DANGER
• The batteries used with the inverters must be approved by the inverter manufacturer. The
list of approved battery can be obtained from our official website.
• A battery short circuit may cause personal injury. The transient high current caused by short
circuit causes release of a large amount of energy, which may cause a fire.
• Before connection of the battery cable, make sure that the power supply has been
disconnected from the inverter and the battery, and the front and rear switches have been
disconnected.
• The positive and negative electrodes of the battery output must be correctly connected with
the inverter, otherwise the transient high current caused by short circuit causes release of a
large amount of energy, which may cause a fire.
• During the operation of the inverter, do not connect or disconnect the battery cable.
Improper operation may cause the electric shock.
• Do not connect a single battery with multiple inverters, otherwise it is possible to damage
the inverters.
• Do not connect the load between the inverter and the battery.
• During connection of the battery cable, use an insulating tool to prevent accidental electric
shock or battery short circuit.
• Make sure that the open-circuit voltage of the battery is within the allowable range of the
inverter.
• Install one DC switch between the inverter and the battery.