OFF
T4
T4HMIN
T4HMAX
Heat mode
by heat
pump
T4_IBH_ON
Heat mode
by IBH only
Heat mode by
heat pump and
IBH
How to set the OTHER HEATING SOURCEt
To set the OTHER HEATING SOURCE, go to MENU>
FOR SERVICEMAN> OTHER HEATING SOURCE,
Press OK. The following page will appear:
If backup heater is available, please select YES at
BACKUP HEATER. Press OK and the following page is
displayed:
When the cursor is on HEAT MODE or DHW MODE, Use
▼
▲
to select YES or NON. If YES is selected, the
backup heater will be available in the corresponding
mode, otherwise it will be unavailable.
When the cursor is on T4_IBH_ON
、
dT1_IBH_ON
、
t_IBH_DELAY
、
or t_IBH12_DELAY, Use
▼
▲
and ▼ ▲
to scroll and adjust the parameter.
T4_IBH_ON is the ambient temperature for starting the
backup heater. If the ambient temperature rises above
T4_IBH_ON, the backup heater will be unavailable. The
relationship between operation of the backup heater and
the ambient is shown in the picture below.
About OTHER HEATING SOURCE
The OTHER HEATING SOURCE is used to set whether
the backup heater, and additional heating sources like a
boiler or solar energy kit is available.
10.7.7 Other HEATING SOURCE
The setting in the user interface should
correspond to the wiring of thermostat. If YES is
selected in ROOM THERMOSTAT and the
MODE SETTING is NON, the wiring of
thermostat should follow method A. If the MODE
SETTING is YES, then the wiring should follow
method B. If “DUAL ROOM THERMOSTAT” is
selected, the wiring of room thermostat should
follow “method C” . (refer to “9.7.6 Connection
for other components/For room thermostat”)
NOTE
YES NON
YES NON
YES NON
SCROLL
7 OTHER HEATING SOURCE
7.1.BACKUP HEATER
7.2.AHS
7.3.SOLAR ENERGY
-5°C
5°C
30MIN
5MIN
YES NON
YES NON
SCROLL
7.1 BACKUP HEATER
HEAT MODE
DHW MODE
T4_IBH_ON
dT1_IBH_ON
t_IBH_DELAY
t_IBH12_DELAY
When the cursor is on HEAT MODE or DHW MODE, Use
▼
▲
to select YES or NON. If YES is selected, the
additional heating source will be available in the
corresponding mode, otherwise it will be unavailable.
If YES is selected in HEAT MODE
,
the
installation of additional heating source should
follow “8.5 Application 5/Applica- -tion a” or “8.5
Application 5/Application b” . IfYES is selected in
DHW MODE, the installation of additional
heating source should follow “8.5 Application
5/Application c”.
NOTE
t_IBH_DELAY is the time that the compressor has run
before the first backup heater turns on (if T1<T1S).
t_IBH12_DELAY is the time that the first backup heater
has run before the second backup heater turns on.
If an additional heating source is available, please select
YES at the corresponding position. Press OK and the
following page is displayed:
T1S-dT1_IBH_ON
IBH1 OFF
IBH1 ON
T1
T1S-dT1_IBH_ON-2
IBH2 OFF
IBH2 ON
T1
T1s-T1
T4
<
T4_IBH_ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
ON
t_IBH_delay
t_IBH12_delay
t_IBH_delay
t_IBH12_delay
dT12
dT1_IBH_ON-2
dT1_IBH_ON
IBH 2
IBH 1
Compressor
dT1_IBH_ON is the temperature difference between T1S
and T1 for starting the backup heater. Only when at the
T1<T1S-dT1_IBH_ON can the backup heater turn on.
When a second backup heater is installed, if the
temperature difference between T1S and T1 is larger than
dT12, the second backup heater will turn on.
The relationship between operation of the backup heater
and the temperature difference is shown in the diagram
below.
7.2 ADDTIONAL HEATING SORUCE
-5°C
5°C
0°C
30MIN
YES NON
YES NON
SCROLL
HEAT MODE
DHW MODE
T4_AHS_ON
dT1_AHS_ON
dT1_AHS_OFF
t_AHS_DELAY
V.1