Unit operation and space heating
:
When a room thermostat is connected to the unit and when there is a heating request from the room thermostat, the unit will
start operating to achieve the target water flow temperature as set on the user interface. When the room temperature is above
the thermostat set point in the heating mode, the unit will stop operating. The circulation pump (1.8) and (10) will also stop
running. The room thermostat is used as a switch here.
The volume of balance tank(8) should be greater than 40L(for 5~9kW unit, greater than 20L) The drain valve (6) should
be installed at the lowest positon of the system. An independent backup heater can be selected and installed in the door.
Pump_o(10) should be controlled by outdoor unit and connect to corresponding port in the outdoor unit(refer to 9.7.6
Connection for other components/For outside circulation pump P_o).
NOTE
Make sure to connect the thermostat wires to the correct terminals, method B should be selected (see "For room
thermostat" in 9.7.6 connection for other components). To correctly configure the ROOM THERMOSTAT in the FOR
SERVICEMAN mode see 10.7 Field settings/ROOM THERMOSTAT.
NOTE
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
2
3
Outdoor unit
Manometer
Pressure relief valve
Expansion vessel
Plate heat exchanger
Backup heater
(
Customized model
)
Air purge valve
Flow switch
P_i: Circulation pump inside the unit
Y-shape filter
Stop valve (field supply)
Assembly unit
Assembly unit
Coding
Coding
4
5
6
7
8
8.1
8.2
9
10
11
FHL 1…n
Wired controller
Room thermostat (field supply)
Drain valve (field supply)
Fill valve (field supply)
Balance tank (field supply)
Air purge valve
Drain valve
Expansion vessel (field supply)
P_o: Outside circulation pump (field supply)
Collector (field supply)
Floor heating loop (field supply)
1
1.6
1.5
1.4 1.2
1.3
1.8
1.7
1.1
8.1
8.2
2 3
6
7
8
FHL1
FHL2
FHLn
----
----
9
T
10
11
4
5
8.2 Application 2
Space heating without room thermostat connected to the unit. Domestic hot water is provided through the domestic hot water
tank that is connected to the unit.
13
V.1