PRODUCT MANUAL UD105
EAE KNX UNIVERSAL DIMMER
UD105 R1
©
EAE Technology
www.eaetechnology.com
Page 20 / 44
5.2.7 Master - Faults
Mains Power Recovery
Dimming value after mains power recovery
*Status as prior to failure
0…100%
This parameter is used to determine the dimming value when the mains power is recovered.
-
Status as prior to failure
:
Channel dimming value will be set as well as before Mains Power
Failure.
Forced Operation Status after mains power
recovery
* Status as prior to failure
Forced Operation disabled
Forced Operation activated
–
Position On
Forced Operation activated
–
Position Off
This parameter is used to determine the Forced Operation status when the mains power is recovered.
-
Status as prior to failure
:
Forced Operation status will be set as well as before Mains Power
Failure.
KNX Bus Failure
Dimming value after KNX bus failure
*
Don’t change
0…100%
This parameter is used to determine the dimming value when KNX Bus Failure.
-
Don’t change
:
Channel dimming value will NOT be changed after KNX Bus Failure.
Forced Operation Status after KNX bus failure
* Keep current status
Forced Operation disabled
Forced Operation activated
–
Position On
Forced Operation activated
–
Position Off
This parameter is used to determine the Forced Operation status when KNX Bus Failure.
-
Keep current status
:
Forced Operation status will not be changed after KNX Bus Failure.