e.g.
Transition time to new brightness= 3 sec
Scene Brightness value= % 25
Current Brightness value= % 60
𝑆𝑐𝑒𝑛𝑒 𝐷𝑖𝑚𝑚𝑖𝑛𝑔 𝑇𝑖𝑚𝑒 = (
𝑇𝑟𝑎𝑛𝑠𝑖𝑡𝑖𝑜𝑛 𝑡𝑖𝑚𝑒 𝑡𝑜 𝑛𝑒𝑤 𝑏𝑟𝑖𝑔ℎ𝑡𝑛𝑒𝑠𝑠
100
) × |𝑆𝑐𝑒𝑛𝑒 𝐵𝑟𝑖𝑔ℎ𝑡𝑛𝑒𝑠𝑠 𝑉𝑎𝑙𝑢𝑒 − 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐵𝑟𝑖𝑔ℎ𝑡𝑛𝑒𝑠𝑠 𝑣𝑎𝑙𝑢𝑒|
The result is = (3/100) x l 25-60 l
=0,03 x l-35l
=0,03 x 35
=1,05 sec
Channel
A…E scene value
*
Don’t change (Not a part of this scene)
0…100%
This parameter is used to select dim value or availability for each channel.