4.4.6
Operating Hour Function
Operating Hour Parameters
The operating hours count the relay on time. The operating hours sums up to determine on time. The
accumulated operating hours are stored in the 2 byte counter. The counter value sends to bus
cyclically or after request. If the voltage fails or ETS programming, all operating hour counter stored
in the devices. After the bus voltage returns, the device updates communication object value.
NOTE: User changed relay position by hand; device cannot detect it so operating hour doesn’t start
the counting.
Counter type
*
up counter
down counter
Up counter:
The operating hours start the count from ’0’. The maximum counting value is 65535
hours. When the operating hour reached limit value, ‘Operating hour runout’ telegram sends to bus.
Then the operating hours counter stop.
Down counter:
The operating hours preset value counting down. When the counter reached ‘0’, the
counting status is reported to the bus via ‘Operating hour runout’.
Limit value preset
no preset
*
set with parameter
set with object
The start or limit value preset here. A limit value can be preset as an option.
§
No preset
For up/down counter the limit value set to 65535. This is the maximum value both of operating
hour.