Product Manual SW108 and SW104
EAE KNX Switch Actuator
PM R2.0
©
EAE Technology
www.eaetechnology.com
Page 9 / 22
§
Set the parameter to “yes”
Operating hour values stored in the device. This means operating hour communication object
will be overwrite operating hour values but ETS download can’t write on it.
§
Set the parameter to “no”
Operating hour values stored in the device with a storage function will be maintained. If no
operating hour values have been stored, the operating hour values last programmed in the ETS
remain valid.
Transmission delay [2…255s] after bus
voltage recovery
*
2
…255
The parameter defines the behaviour of the switch actuator at a bus power return. The transmission
delay time determines the period between bus voltage recovery and the point after which telegrams
can be sent.
Telegram limit active
yes
*
no
Parameter selects “yes”;
Telegram limit period
50ms…*
10s
…1min
The limit period can be adjusted via this parameter.
Max. number of transmitted telegrams
within a period
1…
20
…255
Max number of telegrams per period, can be sent freely.