4.2
Scene
Scene Parameters
The scene function of the switch actuator has an 8 bit scene object. It is possible to define for each
64 scene with parameter window. 8 independent values can be stored for each relay. The scene can
be specified that the relay ‘open contact’ (off), ‘close contact’ (on) or ‘keep position’ its state.
A scene is activated when it receives its scene number at the scene object. The storing of the current
channel values is carried out using the scene object.
For example;
Scene
recall
save
Hex.
Des.
Hex.
Des.
1
0x00
0
0x80
128
2
0x01
1
0x81
129
3
0x02
2
0x82
130
4
0x03
3
0x83
131
5
0x04
4
0x84
132
6
0x05
5
0x85
133
7
0x06
6
0x86
134
8
0x07
7
0x87
135
9
0x08
8
0x88
136
10
0x09
9
0x89
137
11
0x0A
10
0x8A
138
…
…
…
…
…
63
0x3E
62
0xE2
190
64
0x3F
63
0xE3
191