EAE KNX Switch Actuator
Product Manual SW104 and SW108
Страница 1: ...Order Number 48002 EAE KNX Switch Actuator Product Manual SW104 and SW108...
Страница 2: ...3 2 2 Technical Data 5 3 Communication Object Table 6 4 Parameters 7 4 1 Main General 7 4 2 Scene 10 4 3 Channel General 11 4 4 Function 13 4 4 1 Staircase Function 14 4 4 2 External Logic Function 1...
Страница 3: ...enables a convenient control of fluorescent lambs Also device has a manual operating feature The relay can be switched on or off with slide switches The following function list provides Staircase Ext...
Страница 4: ...Product Manual SW108 and SW104 EAE KNX Switch Actuator PM R2 0 EAE Technology www eaetechnology com Page 3 22 2 Device Technology 2 1 Connection Diagram Connection Diagram...
Страница 5: ...4 EAE KNX Switch Actuator PM R2 0 EAE Technology www eaetechnology com Page 4 22 1 Physical Address Label 2 Programming Button 3 Red Programming LED 4 KNX Connection Terminal 5 Switch Position Display...
Страница 6: ...free bistable Installation 35mm mounting rail EN 60 715 Operating elements LED red and button For physical address Temperature range Ambient 5 C 45 C Storage 25 C 55 C Transport 25 C 70 C Humidity max...
Страница 7: ...bit CW 8 23 38 53 68 83 98 113 Output 1 Forced positioning on off DPT_Switch_Control 2 001 2 bit CW 9 24 39 54 69 84 99 114 Output 1 Start value of operating hour 0h 65535 hour DPT_TimePeriodHrs 7 00...
Страница 8: ...s can be modified manually or not Set the parameter to yes Each relay can be operated manually Set the parameter to no It is still possible to change relays position but relay return its old position...
Страница 9: ...t write on it Set the parameter to no Threshold values stored in the device with a storage function will be maintained If no threshold values have been stored the threshold values last programmed in t...
Страница 10: ...ting hour values have been stored the operating hour values last programmed in the ETS remain valid Transmission delay 2 255s after bus voltage recovery 2 255 The parameter defines the behaviour of th...
Страница 11: ...n be specified that the relay open contact off close contact on or keep position its state A scene is activated when it receives its scene number at the scene object The storing of the current channel...
Страница 12: ...y contact closed Switch state on 1 relay contact open Normally open contact Switch state off 0 relay contact open Switch state on 1 relay contact closed Send switch status feedback telegram no after c...
Страница 13: ...y contact open or close after bus voltage return Behaviour bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the outp...
Страница 14: ...eaetechnology com Page 13 22 4 4 Function Function Parameters Above function parameters can be set for each channel These functions I Staircase II External logic III Internal logic IV Priority V Thres...
Страница 15: ...ation of staircase lighting Staircase lighting time is defined by this parameter At the end of the on time the relay off or active the staircase warning functions Staircase retrigger not retriggerable...
Страница 16: ...rcase function Activate pre warning time yes no The warning function can be activated by this parameter select yes Then you can adjust pre warning time number of pre warning and time for pre warning i...
Страница 17: ...ple Switch object value 1 and External logic input object value 0 relay switch as a result of 1 0 operation External logic function type AND OR XOR This parameter selects the type of logic function be...
Страница 18: ...ticipate to the scenario Relay 1 8 state don t care off on To create scenario to open or close channel relay positions of other channels of the switch actuator are set with these parameters The channe...
Страница 19: ...1 byte 0 20000 65535 for 2 byte Threshold limit value enters here This parameter is dependent Object size parameter Threshold reaction OFF 0 below threshold ON 1 above threshold ON 1 below threshold O...
Страница 20: ...y www eaetechnology com Page 19 22 Hysteresis percentage 1 10 1 5 11 For example Hysteresis percentage parameter selected 10 You can see this state below graphic Threshold hysteresis value measure for...
Страница 21: ...nged relay position by hand device cannot detect it so operating hour doesn t start the counting Counter type up counter down counter Up counter The operating hours start the count from 0 The maximum...
Страница 22: ...ic sending and after request The current count of the operating hours can be learned three way cyclic sending after request and cyclic sending and after request 4 4 7 Sweep Function Sweep Parameters S...
Страница 23: ...0 EAE Technology www eaetechnology com Page 22 22 Blink off time 300ms 1sec How long the lights shall be switched off in the period Wait time after blinks sec 0 30 255 How long the lights shall be swi...