F a u l t s a n d s o l u t i o n s

EC6000

 

F a u l t s a n d s o l u t i o n s

EC6000

 

Err11

Motor 

overload

1: P9-23 is set improperly. 
2: The load is too heavy or 
locked rotor occurs on the motor. 
3: The AC drive model is of too 
small power class.

1: Set it correctly. 
2: Reduce the load and check the motor and 
the mechanical condition. 
3: Select an AC drive of higher power 
class.

Err12

Power input 

phase loss

1: The three-phase power input is 
abnormal. 
2: The drive board is faulty. 
3: The lightening board is faulty. 
4: The main control board is 
faulty.

1: Eliminate external faults. 
2: Seek technical support.
3: Seek technical support.
4: Seek technical support.

Err13

Power output 

phase loss

1: The cable connecting the AC 
drive and the motor is faulty. 
2: The AC drive's three-phase 
outputs are unbalanced when the 
motor is running. 
3: The drive board is faulty. 
4: The module is faulty.

1: Eliminate external faults. 
2: Check whether the motor three-phase 
winding is normal. 
3: Seek technical support.
4: Seek technical support. 

Err14

Module 

overheat

1: The ambient temperature is too 
high. 
2: The air filter is blocked. 
3: The fan is damaged.
4: The thermally sensitive 
resistor of the module is damaged. 
5: The inverter module is damaged. 

1: Lower the ambient temperature. 
2: Clean the air filter. 
3: Replace the damaged fan.
4: Replace the damaged thermally 
sensitive resistor. 
5: Replace the inverter module. 

Err15

Err16

 

External 

equipment 

fault

Communi-

cation 

fault

1: External fault signal is input 
via S.

1: The host computer is in 
abnormal state. 
2: The communication cable is 
faulty. 
3: The communication parameters 
in group PB are set improperly.

1:Reset the operation.

1: Check the cabling of host computer. 
2: Check the communication cabling.
3: Set the communication parameters 
properly.

Err17

Err18

Contactor 

faul

Current 

detection 

fault

1: The drive board and power 
supply are faulty. 
2: The contactor is faulty. 

1: The HALL device is faulty. 
2: The drive board is faulty

.

1: Replace the faulty drive board or 
power supply board. 
2: Replace the faulty contactor.

1: Replace the faulty HALL device. 
2: Replace the faulty drive board.

Err19

Motor 

auto-tuning 

fault

1: The motor parameters are not 
set according to the nameplate. 
2: The motor auto-tuning times 
out.

1: Set the motor parameters according 
to the nameplate properly. 
2: Check the cable connecting the AC 
drive and the motor.

Err20

Encoder 

fault

 

1: The encoder type is incorrect. 
2: The cable connection of the 
encoder is incorrect.
3: The encoder is damaged. 
4: The PG card is faulty. 

1: Set the encoder type correctly 
based on the actual situation. 
2: Eliminate external faults.
3: Replace the damaged encoder. 
4: Replace the faulty PG card. 

Err21

Err22

EEPROM 

readwrite 

fault

 

AC drive 

hardware fault

 

1: The EEPROM chip is damaged.

1: Overvoltage exists. 
2: Overcurrent exists.

1: Replace the main control panel.

1: Handle based on over

-

voltage. 

2: Handle based on over

-

current.

Err23

Short circuit 

to ground

1: The motor is short circuited 
to the ground.

1: Replace the cable or motor.

Err24

Err26

EEPORM

 

Initialization

fault

1: Abnormal user data.

1: Reinitialize data and set 
parameters.

Running 

time reached

1: Accumulative running time 
reaches setting.

1: Clear the record through the 
parameter initialization function.

Err29

Power-on time 

reached

Err30

1: Accumulative power-ontime 
reaches the setting.

1: The AC drive running current 
is lower than P9-38

.

1: Clear the record through the 
parameter initialization function.

1: Check the load is disconnected or 
P9-38 and P9-39 is correct.

Load 

becoming 0

Err27

Err28

User-defined 

fault 1

User-defined 

fault 2

1: The user-defined fault 1 signal 
is input via S.

1: Reset the operation.

Err31

Err40

PID feedback 

lost during 

running

Pulse-by-pulse 

current 

limit fault

1: The PID feedback is lower than 
the setting of PA-27.

1: The load is too heavy or 
lockedrotor occurs on the motor. 
2: The AC drive model is of too 
small power class.

1: Check the PID feedback signal or 
set PA-27 to a proper value.

1: Reduce the load and check the 
motor and mechanical condition. 
2: Select the AC drive of higher 
power class.

Err42

Err43

Too large 

speed

 

deviation

Motor 

over-speed

1: The encoder parameters are set 
incorrectly. 
2: The motor auto-tuning is not 
performed. 
3: P9-42 and P9-43 are set 
incorrectly.
1: The encoder parameters are set 
incorrectly. 
2: The motor auto-tuning is not 
performed.
3: P9-40 and P9-41 are set 
incorrectly

1: Set the encoder parameters 
properly. 
2: Perform the motor autotuning. 
3: Set F9-69 and F9-70 correctly 
based on the actual situation.

1: Set the encoder parameters 
properly. 
2: Perform the motor auto-tuning. 
3: Set P9-40 and P9-41 correctly 
based on the actual situation.

Err45

Err51

Motor 

overheat

Pole position

detection

failed

1: The cabling of the temperature 
sensor becomes loose. 
2: The motor temperature is too 
high.

1: The deviation between the motor
parameters and the actual value is
too large.

1: Check the temperature sensor 
cabling and eliminate the cabling 
fault. 
2: Lower the carrier frequency or 
adopt other heat radiation measures.

1: Reconfirm whether the motor 
parameters are correct, and focus on 
whether the rated current is set too 
small. 

Содержание EC6000 Series

Страница 1: ...2 1 in 2023 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Z...

Страница 2: ...by high voltage Never connect the main circuit output terminals U V and W directly to the AC main circuit power supply The circuit board of the AC drive has CMOS IC which is extremely easy to be dama...

Страница 3: ...ation Description of AC drive EC6000 Voltage 220V Voltage 380V Power kW Rated output current A 0 75 1 5 2 2 4 0 5 5 11 7 5 15 18 5 30 22 37 45 55 75 110 90 132 160 200 220 250 280 315 400 350 3 4 4 8...

Страница 4: ...he CLVC mode High performance Power dip ride through Control of asynchronous motor and synchronous motor are implemented through the high performance current vector control technology The load feedbac...

Страница 5: ...rip or salt Altitude Ambient temperature Lower than 1000m Display and operation on the operation panel Optional parts LCD operation panel braking unit I O extension card 1 I O extension card 2 user pr...

Страница 6: ...9 D1 174 194 194 Installation Hole 4 5 6 7 9 30kW 191 120 471 450 242 232 9 0 75kW 1 5kW 2 2kW 4 0kW 5 5kW 11kW 22kW Structure A Structure 380V Class A Structure B Structure 0 75kW 105 94 160 150 137...

Страница 7: ...utput Terminal Commun ication Function Description Voltage or current output is decided by P5 32 Output voltage range 0V 10V Output current range 0mA 20mA Contact driving capacity 250Vac 3A COS 0 4 30...

Страница 8: ...aking unit and braking resistor Err04 Overcurrent at constant speed 1 The output circuit is grounded or short circuited 2 Motor auto tuning is not performed 3 The input voltage is too low 4 A sudden l...

Страница 9: ...is damaged 4 The PG card is faulty 1 Set the encoder type correctly based on the actual situation 2 Eliminate external faults 3 Replace the damaged encoder 4 Replace the faulty PG card Err21 Err22 EE...

Страница 10: ...e primary channel takes precedence Default 0 0 0 0 1 000 0 Auxiliary source Y Gain P0 06 0006H 0 000 5 000 1 000 0 Parameter Name 0008H P0 08 Digital setting of main source X frequency 0 00 Maximum ou...

Страница 11: ...C Drive 55kW 0 1A P1 04 AC Drive 55kW Model dependent P1 12 P1 16 Reserved 010CH 0110H P1 23 Encoder type BIT0 Encoder type 0 ABZ incremental encoder 1 UVW incremental encoder 2 Resolver 3 SIN COS enc...

Страница 12: ...05 P3 06 P3 07 P3 08 P3 09 Parameter Name V F curve selection Multi point V F frequency1 F1 Multi point V F voltage1 V1 Multi point V F frequency2 F2 Multi point V F voltage2 V2 Multi point V F freque...

Страница 13: ...11 Terminal YWN 12 UP and YWN setting clear 13 Speed control Torque control switchover 14 Speed search start enable 15 Reserved 16 Multi reference terminal 1 17 Multi reference terminal 2 18 Multi re...

Страница 14: ...ode after fault reset 0 The terminal operation command is valid immediately 1 The terminal operation command is valid only after it is canceled P4 16 P4 17 P4 18 Terminal protection function selection...

Страница 15: ...100 00 100 00 0509H P5 10 AI2 filter time 0 00 10 00s 0 10s 050AH P5 11 AI3 input voltage minimum value 0 00 10 00V 0 00V 050BH P5 12 AI3 input voltage lower limit corresponding setting 0 00 100 00 0...

Страница 16: ...0 Straight line 1 Curve 0 150 0 00 50 00Hz P6 09 P6 10 P6 11 P6 13 P6 12 P6 08 0609H 060AH 060BH 060DH 060CH 0608H 0 00Hz 0 0 0s 0 0s 00 0 Start of S curve acceleration time End of S curve acceleratio...

Страница 17: ...rs Accumulated running days Accumulated running hours Read only Read only Read only Read only 070BH 0 Chinese 1 English BIT1 Output frequency display selection 0 Target frequency displays the target f...

Страница 18: ...perature reached 0 100 0 65000 BIT0 Motor overload protection selection 0 Invalid 1 Valid BIT1 Ground fault duringpower on 0 Invalid 1 Valid BIT2 Input phase loss protection selection 0 Invalid 1 Vali...

Страница 19: ...00 0A P9 17 Output voltage upon 2nd fault 0911H 0 3000V Read only Read only Read only Read only Read only Read only 0 3000V P9 18 AC drive status upon 2nd fault 0912H Same as P9 10 P9 19 S terminal st...

Страница 20: ...2 P9 52 Protection action selection 3 0000 0934H BIT0 User defined fault 1 Err27 action selection Same as P9 50 BIT0 BIT1 User defined fault 2 Err28 action selection Same as BIT0 BIT2 Power on time ar...

Страница 21: ...help to reduce PID overshoot PA 07 0A07H 00 BIT0 PID shutdown operation 0 Shutdown without calculation 1 Operation when shutdown BIT1 Constant pressure water supply sleep function 0 Invalid 1 Valid B...

Страница 22: ...e first set of transmission frame selection 0 Invalid 1 Run command setting 2 Master set frequency 0031 0B09H 3 Master output frequency 4 Master upper limit frequency 5 Master set torque reserved 6 Ma...

Страница 23: ...0DH 80 0 PD 13 Multi frequency 14 0D0EH 60 0 PD 14 Multi frequency 15 0D10H 10 0 PD 16 Running time of PLC reference 1 0D0FH 0000 PD 15 PLC running mode BIT0 Circulation mode 0 Stop after the AC drive...

Страница 24: ...H 00 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 00 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 00 PD 41 Running direct...

Страница 25: ...A3 03 0 Function code P5 11 setting 1 AI1 2 AI2 3 AI3 4 PULSE setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full range of 1 7 option corresponds to P5 11 A0 01 Torque setting source...

Страница 26: ...48 00Hz 25 00Hz A1 11 A1 12 Add pump frequency 2 Reduce pump frequency 2 0 00 maximum frequency 0 00 A1 11 110BH 110CH 48 00Hz 25 00Hz A1 13 A1 14 Add pump frequency 3 0 00 maximum frequency 0 00 A1 1...

Страница 27: ...s Application mode 1 EC6000 series AC drive has a single master and multi slave control network connected to RS485 bus When the master uses the broadcast command slave address is 0 the slave does not...

Страница 28: ...ieces bytes transmit time START Sub machine address Order code Bytes quantity low position Data address 2100H high position 3 5 pieces bytes transmit time 01H 03H 06H 13H 88H 00H 00H Data address 2100...

Страница 29: ...data bit the number of whole 1 in 1 1 0 0 0 1 0 1 is 4 pieces if use even verifica tion the odd even verification bit of frame will be 0 then obtain the quan tity of whole 1 still be 4 also not proce...

Страница 30: ...inal control 2 RS485 control 3 Option card 4 Terminal switchover AC drive operation status 2100H R BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 10 W Motor control mode 0 V F mode 1 SVC control 2 FVC contro...

Страница 31: ...W Note 1 The function descriptions in brackets are the factory value of AC drive 2 Opticalcoupler isolation compatible ambipolarity input 3 Input impedance 2 4kO 4 Voltage range at electrical level in...

Страница 32: ...uality inverter Warranty Card User Name User Address User Contact Tel Specification Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zheji...

Отзывы: