Control order 

function instruction

Address 

definition

Data meanings instruction

R/W 

characteristics

Communication running 

control order 

Communication 

frequency setting 
Communication set 

upper limit frequency

Communication PID 

give value 

Communication PID 

feedback value

Communication AO1 

output value

Communication AO2 

output value

Communication HDO 

output value

Communication VF 

separate voltage setting

Communication torque 

setting value

2000H

2001H

2002H

2003H

2004H

2005H

2006H

2007H

2008H

2009H

W

W

W

W

W

W

W

W

W

W

BIT0

BIT1

BIT3

BIT4
BIT12-15

BIT2

0-stop order  

1-Running order
0-Corotation order  

1-Reversal order
STOP

 

command

0-No order    

1-Reset order

Jog command

Y1-Y4

Setting range:0-Maximum frequency

Setting range:0-Maximum frequency

Setting range

:0-100.0%

Setting range

:0-100.0%

Setting range

:0-100.0%

Setting range

:0-100.0%

Setting range

:0-50000HZ

Setting range

:0-100.0%

Setting range

:0-100.0%

Monitor command 

function instruction

Address 

definition

Data meanings instruction

R/W 

characteristics

RUN
REV
Ready
Fault

Jogging

Pre-alarm

Auto-turning

Operation control mode

0:Operation panel control

1:Terminal control

2:RS485 control

3:Option card

4:Terminal switchover

AC drive 

operation status

2100H

R

BIT0
BIT1
BIT

2

BIT

3

BIT

4

BIT

5

BIT

6

BIT

7

-

10

W

Motor control mode

0

:V/F 

mode

1:

SVC

 

control

2

FVC

 

control

1  -- ERROR_INVERTER UNIT 

2  -- ERROR_OC_DURING_ACC 

3  -- ERROR_OC_DURING_DEC

4  -- ERROR_OC_AT_CONST_SPEED

5  -- ERROR_OV_DURING_ACC

6  -- ERROR_OV_DURING_DEC

7  -- ERROR_OV_AT_CONST_SPEED

8  -- ERROR_CONTROL POWER SUPPLY

9  -- ERROR_UV

10 -- ERROR_OL_AC DRIVE

11 -- ERROR_OL_MOTOR

12 -- ERROR_LOSE_PHASE_INPUT

13 -- ERROR_LOSE_PHASE_OUTPUT

14 -- ERROR_OH_MODULE

15 -- ERROR_EXTERNAL EQUIPMENT

16 -- ERROR_COMMUNICATE

17 -- ERROR_CONTACTOR

18 -- ERROR_CURRENT_DETECTION

19 -- ERROR_AUTO-TUNING

20 -- ERROR_ENCODER

21 -- ERROR_EEPROM_READWRITE

22 -- ERROR_HARDWARE_AC DRIVE 

23 -- ERROR_MOTOR_SHORT_TO_GND 

24 -- ERROR_ERRPROM_INITIALIZETE   

26 -- ERROR_RUNNING TIME_REACHED

27 -- ERROR_USER-DEFINED_1

28 -- ERROR_USER-DEFINED_2

29 -- ERROR_POWER-ON_TIME_REACHED

30 -- ERROR_LOAD_0

31 -- ERROR_PID_FDB_LOSE 

40 -- ERROR_PBP_CURRENT_LIMIT

41 -- ERROR_SWITCH_MOTOR_WHEN_RUN

42 -- ERROR_TOO_LARGE_SPEED_DEVIATION

43 -- ERROR_MOTOR_OS 

45 -- ERROR_MOTOR_OH

51 -- ERROR_POLE_POSITION_DETECTION

52 -- ERROR_ZERO_POSITION_INDENTIFI-

      CATION

53 -- ERROR_FEEDBACK_UVW_SIGNAL

AC drive 

operation status

AC drive 

fault type

2100H

2101

R

R

BIT

11

-

12

Hibernation sign

BIT

13

R S 4 8 5 c o m m u n i c a t i o n p r o t o c o l

EC6000

 

R S 4 8 5 c o m m u n i c a t i o n p r o t o c o l

EC6000

 

5 6

 -

57 

-

Содержание EC6000 Series

Страница 1: ...2 1 in 2023 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Z...

Страница 2: ...by high voltage Never connect the main circuit output terminals U V and W directly to the AC main circuit power supply The circuit board of the AC drive has CMOS IC which is extremely easy to be dama...

Страница 3: ...ation Description of AC drive EC6000 Voltage 220V Voltage 380V Power kW Rated output current A 0 75 1 5 2 2 4 0 5 5 11 7 5 15 18 5 30 22 37 45 55 75 110 90 132 160 200 220 250 280 315 400 350 3 4 4 8...

Страница 4: ...he CLVC mode High performance Power dip ride through Control of asynchronous motor and synchronous motor are implemented through the high performance current vector control technology The load feedbac...

Страница 5: ...rip or salt Altitude Ambient temperature Lower than 1000m Display and operation on the operation panel Optional parts LCD operation panel braking unit I O extension card 1 I O extension card 2 user pr...

Страница 6: ...9 D1 174 194 194 Installation Hole 4 5 6 7 9 30kW 191 120 471 450 242 232 9 0 75kW 1 5kW 2 2kW 4 0kW 5 5kW 11kW 22kW Structure A Structure 380V Class A Structure B Structure 0 75kW 105 94 160 150 137...

Страница 7: ...utput Terminal Commun ication Function Description Voltage or current output is decided by P5 32 Output voltage range 0V 10V Output current range 0mA 20mA Contact driving capacity 250Vac 3A COS 0 4 30...

Страница 8: ...aking unit and braking resistor Err04 Overcurrent at constant speed 1 The output circuit is grounded or short circuited 2 Motor auto tuning is not performed 3 The input voltage is too low 4 A sudden l...

Страница 9: ...is damaged 4 The PG card is faulty 1 Set the encoder type correctly based on the actual situation 2 Eliminate external faults 3 Replace the damaged encoder 4 Replace the faulty PG card Err21 Err22 EE...

Страница 10: ...e primary channel takes precedence Default 0 0 0 0 1 000 0 Auxiliary source Y Gain P0 06 0006H 0 000 5 000 1 000 0 Parameter Name 0008H P0 08 Digital setting of main source X frequency 0 00 Maximum ou...

Страница 11: ...C Drive 55kW 0 1A P1 04 AC Drive 55kW Model dependent P1 12 P1 16 Reserved 010CH 0110H P1 23 Encoder type BIT0 Encoder type 0 ABZ incremental encoder 1 UVW incremental encoder 2 Resolver 3 SIN COS enc...

Страница 12: ...05 P3 06 P3 07 P3 08 P3 09 Parameter Name V F curve selection Multi point V F frequency1 F1 Multi point V F voltage1 V1 Multi point V F frequency2 F2 Multi point V F voltage2 V2 Multi point V F freque...

Страница 13: ...11 Terminal YWN 12 UP and YWN setting clear 13 Speed control Torque control switchover 14 Speed search start enable 15 Reserved 16 Multi reference terminal 1 17 Multi reference terminal 2 18 Multi re...

Страница 14: ...ode after fault reset 0 The terminal operation command is valid immediately 1 The terminal operation command is valid only after it is canceled P4 16 P4 17 P4 18 Terminal protection function selection...

Страница 15: ...100 00 100 00 0509H P5 10 AI2 filter time 0 00 10 00s 0 10s 050AH P5 11 AI3 input voltage minimum value 0 00 10 00V 0 00V 050BH P5 12 AI3 input voltage lower limit corresponding setting 0 00 100 00 0...

Страница 16: ...0 Straight line 1 Curve 0 150 0 00 50 00Hz P6 09 P6 10 P6 11 P6 13 P6 12 P6 08 0609H 060AH 060BH 060DH 060CH 0608H 0 00Hz 0 0 0s 0 0s 00 0 Start of S curve acceleration time End of S curve acceleratio...

Страница 17: ...rs Accumulated running days Accumulated running hours Read only Read only Read only Read only 070BH 0 Chinese 1 English BIT1 Output frequency display selection 0 Target frequency displays the target f...

Страница 18: ...perature reached 0 100 0 65000 BIT0 Motor overload protection selection 0 Invalid 1 Valid BIT1 Ground fault duringpower on 0 Invalid 1 Valid BIT2 Input phase loss protection selection 0 Invalid 1 Vali...

Страница 19: ...00 0A P9 17 Output voltage upon 2nd fault 0911H 0 3000V Read only Read only Read only Read only Read only Read only 0 3000V P9 18 AC drive status upon 2nd fault 0912H Same as P9 10 P9 19 S terminal st...

Страница 20: ...2 P9 52 Protection action selection 3 0000 0934H BIT0 User defined fault 1 Err27 action selection Same as P9 50 BIT0 BIT1 User defined fault 2 Err28 action selection Same as BIT0 BIT2 Power on time ar...

Страница 21: ...help to reduce PID overshoot PA 07 0A07H 00 BIT0 PID shutdown operation 0 Shutdown without calculation 1 Operation when shutdown BIT1 Constant pressure water supply sleep function 0 Invalid 1 Valid B...

Страница 22: ...e first set of transmission frame selection 0 Invalid 1 Run command setting 2 Master set frequency 0031 0B09H 3 Master output frequency 4 Master upper limit frequency 5 Master set torque reserved 6 Ma...

Страница 23: ...0DH 80 0 PD 13 Multi frequency 14 0D0EH 60 0 PD 14 Multi frequency 15 0D10H 10 0 PD 16 Running time of PLC reference 1 0D0FH 0000 PD 15 PLC running mode BIT0 Circulation mode 0 Stop after the AC drive...

Страница 24: ...H 00 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 00 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 00 PD 41 Running direct...

Страница 25: ...A3 03 0 Function code P5 11 setting 1 AI1 2 AI2 3 AI3 4 PULSE setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full range of 1 7 option corresponds to P5 11 A0 01 Torque setting source...

Страница 26: ...48 00Hz 25 00Hz A1 11 A1 12 Add pump frequency 2 Reduce pump frequency 2 0 00 maximum frequency 0 00 A1 11 110BH 110CH 48 00Hz 25 00Hz A1 13 A1 14 Add pump frequency 3 0 00 maximum frequency 0 00 A1 1...

Страница 27: ...s Application mode 1 EC6000 series AC drive has a single master and multi slave control network connected to RS485 bus When the master uses the broadcast command slave address is 0 the slave does not...

Страница 28: ...ieces bytes transmit time START Sub machine address Order code Bytes quantity low position Data address 2100H high position 3 5 pieces bytes transmit time 01H 03H 06H 13H 88H 00H 00H Data address 2100...

Страница 29: ...data bit the number of whole 1 in 1 1 0 0 0 1 0 1 is 4 pieces if use even verifica tion the odd even verification bit of frame will be 0 then obtain the quan tity of whole 1 still be 4 also not proce...

Страница 30: ...inal control 2 RS485 control 3 Option card 4 Terminal switchover AC drive operation status 2100H R BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 10 W Motor control mode 0 V F mode 1 SVC control 2 FVC contro...

Страница 31: ...W Note 1 The function descriptions in brackets are the factory value of AC drive 2 Opticalcoupler isolation compatible ambipolarity input 3 Input impedance 2 4kO 4 Voltage range at electrical level in...

Страница 32: ...uality inverter Warranty Card User Name User Address User Contact Tel Specification Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zheji...