2 2
-
-
23
-
F u n c t i o n C o d e T a b l e
EC6000
F u n c t i o n C o d e T a b l e
EC6000
P3
-
16
0.1~1000.0s
0V~rated motor voltage
10.0s
0V
P3
-
17
030FH
0310H
Voltage digital
setting for
V/F separation
Voltage
acceleration
time of V/F
separation
Voltage
deceleration
time of V/F
separation
0.1~1000.0s
10.0s
0311H
P3
-
18
P3
-
19
P3
-
20
P3
-
21
V/F separation
shutdown mode
0:Frequency/voltage independent reduction
to 0.
1:After the voltage is reduced to 0,the
frequency is reduced to 0 again.
0
0312H
50~200%
150%
0312H
Overcurrent stall
action current
0:Invalid 1:Valid
1
0312H
Overcurrent stall
suppression
enable
P3
-
22
50~200%
0~100
50%
20
P3
-
23
0312H
0312H
Stall current
compensation
factor
Overvoltage
stall action
voltage
200.0V~2000.0V
220V:380V 690V:1250V
380V:760V 1140V:1900V
480V:850V
Model
dependent
0312H
P3
-
24
P3
-
25
P3
-
26
P3
-
27
Overvoltage
stall enable
1
0312H
0~100
30
0312H
Overvoltage stall
frequency gain
Overcurrent stall
suppression gain
0:Invalid 1:Valid
Overvoltage stall
voltage gain
0~100
30
0312H
P3
-
28
P3
-
29
P3
-
30
Overvoltage
stall maximum
frequnency
5Hz
0312H
0~1
0
0312H
Automatic up-
scaling enable
0~50Hz
Minimum electric
torque current
0A~64A
32A
0312H
P3
-
31
Minimum
generation
torque current
10~100%
20%
0312H
P3
-
32
0~100
30
0312H
Automatic up-
scaling KP
P3
-
33
0~100
30
0312H
Automatic up-
scaling KI
P4
In p ut Te r min a ls fu n cti o n
0: No function 1: Forward RUN (FWD)
2: Reverse RUN (REV) 3: Three-Wire control
4: Forward JOG (FJOG) 5: Reverse JOG (RJOG)
6: Coast to stop 7: Emergency stop
8: Fault reset (RESET)
9: External fault input
10:Terminal UP
11:Terminal YWN
12:UP and YWN setting clear
13:Speed control/Torque control switchover
14:Speed search start enable
15:Reserved
16:Multi-reference terminal 1
17:Multi-reference terminal 2
18:Multi-reference terminal 3
19:Multi-reference terminal 4
20:Terminal 1 for acceleration/deceleration
time selection
21:Terminal 2 for acceleration/deceleration
time selection
22:Acceleration/Deceleration prohibited
23:PID control cancel
24:PID control pause
25:PID integral pause
26:PID characteristic switching
27:PID parameter switchover
28:PID target value switchover terminal1
29:PID target value switchover terminal2
30:PID target value switchover terminal3
31:PID feedback value switchover terminal1
32:PID feedback value switchover terminal2
33:PID feedback value switchover terminal3
34:PLC pause 35:PLC status reset
36:Swing enable 37:Swing pause
38:Swing reset
39:Frequency source switchover terminal1
40:Frequency source switchover terminal2
41:Frequency source switchover terminal3
42:Frequency source switchover terminal4
43:Command source switchover terminal 1
44:Command source switchover terminal 2
45:Counter input terminal
46:Counter reset terminal
47:Counter clock input terminal
48:Counter reset
49:DC braking command
50:Terminal pre-excitation
51: User-defined fault1
52: User-defined fault2
53:Pump 1 invalid 54: Pump 2 invalid
55: Pump 3 invalid 56: Pump 4 invalid
P4
-
00
Function
Code
S1 terminal
function
Parameter Name
Setting Range
1
Default
0400H
Address
P4
-
01
S2 terminal
function
2
0401H
P4
-
02
S3 terminal
function
4
0402H
P4
-
03
S4 terminal
function
5
0403H
P4
-
04
S5 terminal
function
6
0404H
P4
-
05
S6 terminal
function
8
0405H
P4
-
06
S7 terminal
function
10
0406H
P4
-
07
S8 terminal
function
11
0407H