Страница 1: ... GNExS1RAC230 115Vac 100 260Vac 50 60Hz 73mA 80mA 110 105 230Vac 48mA GNExS1FDC024 12Vdc 10 30Vdc 221mA 221mA 115 110 24Vdc 185mA GNExS1FDC048 48Vdc 38 60Vdc 115mA 221mA 115 110 GNExS1FAC230 115Vac 100 260Vac 50 60Hz 73mA 80mA 115 110 230Vac 48mA Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The current levels shown above are for the 440Hz Continuous tone n...

Страница 2: ...4 Gb for Ta 60 C to 70 C Certificate No SIRA 13ATEX1139X IECEx SIR 13 0029X CSAE 21UKEX1558X Epsilon x Equipment Group and Category II 2G CE Marking and Notified Body No 2813 UKCA Marking and Notified Body No 0518 4 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification Zone 1 Explosive gas air mixture likel...

Страница 3: ... to ensure that they are clean and that they have not been damaged during installation Ensure that the O ring seal is in place and undamaged When fitting the flameproof cover ensure the thread is engaged correctly Fully tighten the cover all the way ensure no gap is visible between the cover and base of the sounder enclosure Tighten the M3 grub screw 7 Installation Requirements 7 1 Installation St...

Страница 4: ...the cable entry or the cable branching point temperatures may exceed 70ºC at entry point 80ºC at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated in the table below Max Ambient Temperature ºC Model 40 45 50 55 60 65 70 GNExS1 70 75 80 85 90 95 Table 2 Min Ratings of Cables Cable Glands Cable Glands Appropriat...

Страница 5: ...ion The GNExS Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP 2witch 2 see figures 6 and 7 on the PCB for stage 1 and stage 2 respectively Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 Figure 9 DIP switch configuration The sounder can also be switched to s...

Страница 6: ...figuration 1 2 AC Two Three Stage Voltage Free Activation Configuration K Table 3 Summary of Wiring Options 9 End of Line Monitoring DC Units All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber If an end of line resistor is used it must h...

Страница 7: ...ed prior to opening the unit Electrostatic charging hazard Clean only with a damp cloth 11 SIL 2 Reliability Data Reliability and Functional safety IEC EN61508 which has been assessed and is considered suitable for use in low demand safety function 1 Random Hardware Failures and Architectural constraints route 2H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was asses...

Страница 8: ...E MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve R1 R1 S2 R1 S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Singl...

Страница 9: ...ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Set H1 H2 to ve switching Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Config...

Страница 10: ...r to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 Cconnect Stage 2 ve to Common ve Stage 3 Connect both Stage 1 ve Stage 2 ve to Common ve CUSTOM CONFIGURATION PRODUCT OPTION Y Cut Link W1 H2 H1 Set H1 H2 to ve switching CUSTOM CONFIGURATION PRODUCT...

Страница 11: ...Page left Intentionally blank ...

Страница 12: ... 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0 1 1...

Страница 13: ...Page left Intentionally blank ...

Страница 14: ...dy No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T3 T4 T5 or T6 Gb Standards applied EN 60079 0 2018 EN 60079 1 2014 A C 2018 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 6...

Страница 15: ...ate and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the m...

Страница 16: ...uipment II 2G Ex db IIB or IIC T3 T4 T5 or T6 Gb Standards applied EN 60079 0 2018 EN 60079 1 2014 A C 2018 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain hazardous substances in electrical and electronic equipmen...