European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D157-00-001-IS

 

Issue 9

 

28-11-22

Sheet 4 of 7

 

 

Figure 5: GNExS1 Entries and Terminal Block Location. 

 

When connecting wires to the terminals great care should be 
taken to dress the wires so that when the cover is inserted into 
the  chamber  the  wires  do  not  exert  excess  pressure  on  the 
terminal  blocks.  This  is  particularly  important  when  using 
cables with large cross-sectional areas such as 2.5mm². 
 

Earthing 

 
Please note that for AC supply voltage product versions the 
Earth terminal on the PCBA does not provide an earth 
connection to the product enclosure. The enclosure must be 
independently earthed using either the external or internal 
earth fixing point, (see fig 5 and notes below). 
 
Both AC and DC sounder units must be connected to an earth 
according  to  EN/IEC  60079/14.  The  units  are  provided  with 
internal and external earth terminals which are both located on 
the terminal chamber section of the unit (see figure 5). 

 

Internal earthing connections should be made to the Internal 
Earth Stud of the housing using a ring crimp terminal to secure 
the  earth  conductor  between  the  two  M4  stainless  steel  flat 
washers. The earth conductor should be at least equal in size 
and rating to the incoming power conductors. 
 
External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth conductor 
to  the  earth  stud  between  the  two  M5  stainless  steel  flat 
washers, then reassemble the M5 spring washer and tighten 
the  M5  nut  to  ensure  that  the  cable  lug  is  secured  against 
loosening and twisting. The external earth conductor should be 
at least 4mm

2

 in size. 

 

1.1. Cable Glands, Blanking Elements & Adapters 

 
For  high  ambient  temperatures  the  cable  entry  or  the  cable 
branching point temperatures may exceed: 
 

  70ºC at entry point. 

  80ºC at branching point. 

 

Therefore,  suitable  heat  resisting  cables  and  cable  glands 
must  be  used,  with  a  rated  service  temperature  at  least  as 
stated in the table below: 

 

Max Ambient Temperature (ºC)

 

Model 

40 

45 

50 

55

60 

65 

70

GNExS1 

 

70 

75 

80

85 

90 

95

Table 2: Min. Ratings of Cables & Cable Glands. 

 
 

Cable Glands 

 
Appropriate cable glands to be customer supplied. 
 
The cable entries have an M20 x 1.5 – 6H entry thread. Only 
suitably rated and certified cable glands must be used. They 
must be suitable for the type of cable being used and also meet 
the  requirements  of  the  current  installation  standards  EN 
60079-14 / IEC60079-14. 
 

Blanking Plugs 
 

When only one cable entry is used the other entries must be 
closed with suitably rated and certified blanking plugs as per 
type of approval. 
 
Any unused cable entries must be closed with suitably rated 
blanking plugs. 
 

Ingress Protection 

 
If  a  high  IP  (Ingress  Protection)  rating  is  required,  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs. A minimum ingress protection rating of IP6X 
must  be  maintained  for  installations  in  explosive  dust 
atmospheres. 
 

Adapters 

 
The GNEx sounder range can be supplied with the following 
types of adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 

It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 

 
 

Any other adapters used must be suitably rated. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 

8)  Settings 

 
Following illustrations show the settings available for GNExS1 
Alarm Horn Sounders. See schematic diagrams D190-06-001 
for DC units and D190-06-005 for AC units. 
 

8.1  SPL Configuration 

 
See  Table  1  for  product  power  supply  and  Sound  Pressure 
Levels (SPL). 
 

Configuration for DC Units 

 

Содержание GNExS1

Страница 1: ... GNExS1RAC230 115Vac 100 260Vac 50 60Hz 73mA 80mA 110 105 230Vac 48mA GNExS1FDC024 12Vdc 10 30Vdc 221mA 221mA 115 110 24Vdc 185mA GNExS1FDC048 48Vdc 38 60Vdc 115mA 221mA 115 110 GNExS1FAC230 115Vac 100 260Vac 50 60Hz 73mA 80mA 115 110 230Vac 48mA Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The current levels shown above are for the 440Hz Continuous tone n...

Страница 2: ...4 Gb for Ta 60 C to 70 C Certificate No SIRA 13ATEX1139X IECEx SIR 13 0029X CSAE 21UKEX1558X Epsilon x Equipment Group and Category II 2G CE Marking and Notified Body No 2813 UKCA Marking and Notified Body No 0518 4 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification Zone 1 Explosive gas air mixture likel...

Страница 3: ... to ensure that they are clean and that they have not been damaged during installation Ensure that the O ring seal is in place and undamaged When fitting the flameproof cover ensure the thread is engaged correctly Fully tighten the cover all the way ensure no gap is visible between the cover and base of the sounder enclosure Tighten the M3 grub screw 7 Installation Requirements 7 1 Installation St...

Страница 4: ...the cable entry or the cable branching point temperatures may exceed 70ºC at entry point 80ºC at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated in the table below Max Ambient Temperature ºC Model 40 45 50 55 60 65 70 GNExS1 70 75 80 85 90 95 Table 2 Min Ratings of Cables Cable Glands Cable Glands Appropriat...

Страница 5: ...ion The GNExS Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP 2witch 2 see figures 6 and 7 on the PCB for stage 1 and stage 2 respectively Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 Figure 9 DIP switch configuration The sounder can also be switched to s...

Страница 6: ...figuration 1 2 AC Two Three Stage Voltage Free Activation Configuration K Table 3 Summary of Wiring Options 9 End of Line Monitoring DC Units All DC units have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals in the flameproof chamber If an end of line resistor is used it must h...

Страница 7: ...ed prior to opening the unit Electrostatic charging hazard Clean only with a damp cloth 11 SIL 2 Reliability Data Reliability and Functional safety IEC EN61508 which has been assessed and is considered suitable for use in low demand safety function 1 Random Hardware Failures and Architectural constraints route 2H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was asses...

Страница 8: ...E MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve R1 R1 S2 R1 S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Singl...

Страница 9: ...ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Set H1 H2 to ve switching Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Config...

Страница 10: ...r to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 Cconnect Stage 2 ve to Common ve Stage 3 Connect both Stage 1 ve Stage 2 ve to Common ve CUSTOM CONFIGURATION PRODUCT OPTION Y Cut Link W1 H2 H1 Set H1 H2 to ve switching CUSTOM CONFIGURATION PRODUCT...

Страница 11: ...Page left Intentionally blank ...

Страница 12: ... 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0 1 1...

Страница 13: ...Page left Intentionally blank ...

Страница 14: ...dy No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T3 T4 T5 or T6 Gb Standards applied EN 60079 0 2018 EN 60079 1 2014 A C 2018 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 6...

Страница 15: ...ate and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the m...

Страница 16: ...uipment II 2G Ex db IIB or IIC T3 T4 T5 or T6 Gb Standards applied EN 60079 0 2018 EN 60079 1 2014 A C 2018 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain hazardous substances in electrical and electronic equipmen...

Отзывы: