European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D157-00-001-IS
Issue 9
28-11-22
Sheet 6 of 7
Config. Voltage
Configuration Description
Features
Product
Option
Identifier
See documents D190-06-001 for DC schematic diagrams.
1a
DC
Single Stage Configuration
Line monitoring
Positive Switching
1
1b
DC
Two Stage Configuration
Common Negative
Positive Switching
1
1c
DC
Three/Four Stage Configuration
Common Negative
Positive Switching
1
2
DC
Three/Four Stages. Voltage Free 2nd, 3rd &
4th Stage Activation Configuration
Common Positive
Customer Set H1 & H2 to Negative
Switching
1
3
DC
Two Stage Configuration
Independent Stage Input
Reverse Polarity Stage Monitoring
1
4
DC
Two Stage Configuration
Line Stage Monitoring (Use suitable
monitoring relays/ modules)
Not to be used in reverse polarity
monitoring
Y
5
DC
Two/Three Stage Voltage Free Activation
Configuration
K
6
DC
Three/Four Stage Configuration
Independent Stage Input
Line Stage Monitoring (Use suitable
monitoring relays/ modules)
Positive Switching (Default)
V
See documents D190-06-005 for AC schematic diagrams.
1a
AC
Single Stage Configuration
1
1b
AC
Three/Four Stage Configuration
1
2
AC
Two/Three Stage Voltage Free Activation
Configuration
K
Table 3: Summary of Wiring Options.
9) End of Line Monitoring (DC Units)
All DC units have a blocking diode fitted in their supply input
lines. An end of line monitoring diode or an end of line
monitoring resistor can be connected across the +ve and –ve
terminals in the flameproof chamber. If an end of line resistor
is used it must have a minimum resistance value of 3k3 ohms
and a minimum wattage of 0.5W or a minimum resistance
value of 500 ohms and a minimum wattage of 2W.
The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor
leads should be kept as short as possible. See D190-06-001
for details.
Figure 10: End of Line Resistor placement.
Note that the maximum forward polarity monitoring voltage is
6V. A monitoring voltage greater than 6V may activate the
alarm horn sounder and the 2nd, 3rd or 4th stages.
9.1 Custom DC Multi-Stage End Of Line Monitoring
An optional 12-way terminal module is available to enable up
to four alarm stages to be activated from three DC voltage
output channels. The three alarm stage activation inputs can
be independently monitored.
Refer to Schematic D190-06-001, Config. 6.
Specify Product option ‘V’ when ordering.
Spare part code for field installation: SP78-0001
Figure 11: End of Line Resistor placement – Optional 12-Way
Terminal Module.