INSTRUCTION MANUAL 

D1xB2LD2 LED Beacon 

 

For use in Hazardous Locations

 

 

 

 
 
 
 
 
 
 
 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 DO NOT PAINT 

 TO REDUCE THE RISK OF IGNITION OF 

HAZARDOUS ATMOSPHERES, THE FIRST 
CONDUIT RUN MUST HAVE A SEALING 
FITTING CONNECTED WITHIN 18 INCHES 
OF ENCLOSE. SUBSEQUENT CONDUIT 
RUNS MUST HAVE A SEALING FITTING 
CONNECTED AS CLOSE AS PRACTICAL TO 
THE WALL OF THE ENCLOSURE, BUT IN 
NO CASE MORE THAN THE SIZE OF THE 
CONDUIT OR 50MM, WHICHEVER IS THE 
LESSER. 

 TO PREVENT IGNITION OF GROUP A, B, C 

AND D ATMOSPHERES - SEE       
INSTRUCTION FOR CHEMICAL 
COMPATIBILITY 

 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 NE PAS PEINTURER 

 POUR RÉDUIRE LE RISQUE 

D'INFLAMMATION DES ATMOSPHÈRES 
DANGEREUSES, LE PREMIER CONDUIT DE 
CONDUIT DOIVENT AVOIR UN RACCORD 
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18 
POUCES DE L'ENFERMEMENT. POUR 
SUBSÉQUENT LES

 

CONDUITES DE 

CONDUIT LA DISTANCE ENTRE LA 
SURFACE DE LA MASSE DE REMPLISSAGE 
AU PLUS PRÈS DE L’ENVELOPPE DOIT 
ÊTRE AUSSI PETITE QUE CE QUI EST 
RÉALISABLE MAIS EN AUCUN CAS 
SUPÉRIEURE À LA PLUS PETITE DES 
DIMENSIONS CORRESPONDANT À LA 
TAILLE DU CONDUIT OU À 50 MM. 

 POUR PRÉVENIR L'INFLAMMATION DES 

ATMOSPHÈRES DES GROUPES A, B, C ET 
D-VOIR L'INSTRUCTION POUR LA 
COMPATIBILITÉ CHIMIQUE 

2)  Rating & Marking Information 

 

2.1 NEC & CEC Class / Division Ratings for US / Canada 

 
The D1xB2LD2 LED beacons comply with the following 
standards: 
 

UL 1203 (Ed. 5) 2015 
CSA C22.2 No. 30-M1986 (Ed. 1) 2003 
CSA C22.2 No. 25 (Ed. 4) 2017 
CSA C22.2 No. 205 (Ed. 3) 2017 
 

 
The D1xB2LD2 LED Beacon is rated as follows: 

Class I Div 1 Group ABCD T5 Ta -55°C to +80°C 
Class I Div 1 Group ABCD T6 Ta -55°C to +75°C 
Class II Div 1 Group EFG T5 Ta -55°C to +80°C 
Class III Div 1 Ta -55°C to +80°C 

 

Installation must be carried out in compliance with the 
National Electric Code / Canadian Electric Code 

 
2.2 NEC Class / Zone ratings US 

 
The D1xB2LD2 LED beacons comply with the following 
standards: 

 

UL 60079-0-2013 
UL 60079-1-2015 
UL 60079-31-2015 
 

The D1xB2LD2 LED Beacon is rated as follows: 

Class I Zone 1 AEx db IIC T5 Ta -55°C to +80°C 
Class I Zone 1 AEx db IIC T6 Ta -55°C to +70°C 
Zone 21 AEx tb IIIC T100°C Ta -55°C to +80°C 

 

Installation must be carried out in compliance with the 
National Electric Code. 

 
2.3 CEC Class / Zone ratings Canada 
 

The D1xB2LD2 LED beacons comply with the following 
standards: 

CAN/CSA C22.2 No. 60079-0-2015 
CAN/CSA C22.2 No. 60079-1-2016 
CAN/CSA C22.2 No. 60079-31-2015 

 

The D1xB2LD2 LED Beacon is rated as follows: 

Ex db IIC T5 Ta -55°C to +80°C 
Ex db IIC T6 Ta -55°C to +70°C 
Ex tb IIIC T100°C Ta -55°C to +80°C 

 

Installation must be carried out in compliance with the 
Canadian Electric Code 
 
 
 
 
 
 
 
 
 