European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e-2-s.com              Fax: +44 (0)208 740 4200 
Document No. D210-00-681-IS 

Issue 3          20-04-2020                         Sheet 1 of 8

 

                                                                                              

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExCTS110-05D-P and BExCTS110-05D-R-P Combined 

Sounder / Beacon with Call Relay For use in Flammable Gas 

and Dust Atmospheres

 

 

 

 

 

 

 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGIZED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD 

– CLEAN ONLY WITH A DAMP 

CLOTH 

 COVER BOLTS CLASS A4-80 

 USE HEAT RESISTING CABLES AND CABLE 

GLANDS (RATED 110°C) AT AMB. 
TEMPERATURES OVER 40°C 

 

2)  Rating & Marking Information 

 

All  units  have  a  rating  label,  which  carries  the  following 
important information: - 

 

Model No.:

  

BExCTS110-05D-P or BExCTS110-05D-R-P 

 

Input Voltage:

  DC Units    12V or 24V or 48V 

AC Units    115V or 230V 

 

BExCTS110-05D-P or BExCTS110-05D-R-P Codes:  

Ex db IIB T5 Gb Ta. -50°C to +40°C 
Ex db IIB T4 Gb Ta. -50°C to +70°C 
Ex tb IIIC T110°C Db Ta. -50°C to +55°C 
Ex tb IIIC T125°C Db Ta. -50°C to +70°C 

 

Certificate No.

  KEMA 01ATEX2223X 

IECEx KEM 10.0025X 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

The units can be installed in locations with the following 
conditions: 

 

Area Classification Gas: 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  atmosphere  not  likely  to 
occur  in  normal  operation  but  may  be 
present for short periods. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

 

Temperature Classification: 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

T5 

100ºC (up to 40

°C

 ambient) 

 

Area Classification Dust: 

Zone 21 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

Explosive  dust  air  mixture  not  likely  to 
occur in normal operation, and if it does, it 
will only exist for a short time. 

 

Dust Groupings: 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dust 

Group IIIC 

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

110ºC at +55 ºC ambient 
125 ºC at +70 ºC ambient 

 

IP Rating:  

IP66/67 to EN/IEC60529 and IP6X to 
EN/IEC60079-0, EN/IEC60079-31 

 

Equipment Category:

 

2G / 2D 

 

Equipment Protection Level:

 

Gb / Db 

 

Ambient Temperature Range:

 

-50°C to +70°C Gas Groups IIA and IIB 
-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

2813 

II 2G 
II 2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

BExCTS110-05D-P 

BExCTS110-05D-R-P 

Содержание BExCTS110-05

Страница 1: ...C Db Ta 50 C to 55 C Ex tb IIIC T125 C Db Ta 50 C to 70 C Certificate No KEMA 01ATEX2223X IECEx KEM 10 0025X The units can be installed in locations with the following conditions Area Classification...

Страница 2: ...he combined sounder beacon should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the unit The BEx...

Страница 3: ...lanking devices during installation according to EN IEC60079 14 If a high IP Ingress Protection rating is required then a suitable sealing washer must be fitted under the cable glands or blanking plug...

Страница 4: ...le should enter through the other M20 entry Connect the power input L to the telephone board L terminal in the sounder section power input N to the beacon board N terminal in the beacon section Connec...

Страница 5: ...seven shows the switch positions 1 4 for the country setting and switch 5 for the beacon continuous or pulse mode and switch 6 for the sounder continuous or pulse mode When making any changes to the...

Страница 6: ...n in figure 11 Fig 11 Cover and Guard Fixtures 16 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance...

Страница 7: ...lephone Selection Settings DIP Switch Settings DIP Switch Settings Dialing Country Setting 1 2 3 4 5 6 Australia Ireland New Zealand Singapore South Africa UK 0 0 0 0 Belgium Canada Cyprus Hong Kong S...

Страница 8: ...1 0 Tone 31 Tone 1 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 Tone 4 Tone 5 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 Tone 15 Tone 5 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 Tone 4 Tone 5 15...

Отзывы: