European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2446-P      Issue C        23-04-10                       

Sheet 1 of 6

 

  

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExCS110-L1D 

Flameproof Combined Sounder / LED Beacon 

 
 
 
 
 
 

1)  Introduction 

 
The BExCS110-L1D is a flameproof combined sounder / LED 

beacon which is certified meet the requirements of the ATEX 
directive 94/9/EC and the IECEx Scheme. The combined unit 

produces both loud audio warning signals and visual warning 
signals  that  can  be  used  in  hazardous  areas  where 

potentially  flammable  atmospheres  may  be  present.  Thirty-
two different first stage audio alarm sounds can be selected 

by  internal  switches,  and  each  one  can  be  externally 

changed  to  a second or  third  stage  alarm sound   (

see  tone 

table on Page 5

).  The sounder produces output levels in the 

110dB(A) range. Nine different flash patterns can be selected 
including  a  steady  ON  state  and  can  also  be  remotely 

switched to a second and third flash pattern (

see flash pattern 

table on page 5). 

The unit can be used in Zone 1 and Zone 2 

areas with gases in groups IIA and IIB and with Temperature 
Classifications of T1, T2, T3 and T4.  
 

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 

important information:- 
 
Unit Type No.     

       BExCS110-L1D

 

 
Input Voltage:    DC Units    12V  or 24V  or  48V 

            AC Units         230V or 115V 

 

        

Code:                

Ex d IIB T4 for T

a

 –50

°

C to +70

°

C

 

 

 

Certificate No.

     KEMA 01ATEX2223X 

 

 

IECEx KEM 10.0025X

 

 

 

 

 

 
 

“Warnings”

 

 

DO NOT OPEN WHEN AN EXPLOSIVE  

                         

     GAS ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 

                    USE HEAT RESISTING CABLES AND        

                   CABLE GLANDS (Rated 110ºC) AT  

                       AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  

Serial No.       

 

 i.e.  10 / 1CS51000001 

 

3) 

Type Approval Standards

 

 

The units have an EC Type examination certificate issued by 

KEMA and have been approved to the following standards:- 

 

 
 

 
 

 
 
 
EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

 

4) 

Installation Requirements

 

 

The  unit  must  be  installed  in  accordance  with  the  latest 
issues of the relevant parts of the EN60079 specifications or 

the equivalent IEC specifications – Selection, Installation and 
maintenance  of  electrical  apparatus  for  use  in  potentially 
explosive  atmospheres  (other  than  mining  applications  or 

explosive processing and manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The  installation  of  the  unit  must  also be  in  accordance  with 
any  local  codes  that  may  apply  and  should  only  be  carried 

out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

 

5) 

Zones, Gas Group, Category and Temperature 
Classification 

 

The BExCS110-L1D unit has been certified Ex d IIB T4 for T

a

 

–50

°

C to +70

°

C. This means that the units can be installed in 

locations with the following conditions:- 
  

Area Classification: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if  it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

  

 
Equipment Category:

 

2G 

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

 
 

Ambient Temperature Range: 

 

   

         -50

°

C to +70

°

 

0518 

II 2G 

Epsilon x: 

Equipment Group 
and Category: 

CE Marking: 

Notified Body No. 
 