INSTRUCTION MANUAL
BExCBL2-L2D-P
Combined Beacon/ Beacon
ATEx/IECEx & UKEx Gas & Dust
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D210-00-721-IS
Issue 5
12-09-2022
Sheet 1 of 6
BExCBGL2-L2D-P
1. Product Table
Unit Type Code
Nominal
Input
Voltage
Chamber
Beacon
Nominal
Input Current
Cover Beacon
Nominal
Input Current
Max I/P Voltage
BExCBGL2-L2DPDC024
24Vdc
240mA
240mA
28V
BExCBGL2-L2DPAC115
115Vac
85mA
85mA
126V
BExCBGL2-L2DPAC230
230Vac
48mA
48mA
253V
The table shows the input current taken by the various units.
Nominal current at nominal voltage.
Table 1: Electrical Ratings.
It is important that a suitable power supply is used to run the equipment. The power supply selected must have the necessary capacity
to provide the input current to all of the units.
The above table shows the input current taken by the various units and shows the maximum voltage at which they can be operated:
The input current will vary according to the voltage input level and flash rates selected.
2. Warnings
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGIZED
POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A DAMP CLOTH
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND CABLE GLANDS (RATED 110°C) AT AMB. TEMPERATURES OVER
40°C