3.  Marking & Rating Information 

The  BExCBGL2-L2D-P  Alarm  Horns  comply  with  the  following 
standards for hazardous locations:  
  

3.1 ATEX / IECEx & UKEx Ratings

 

 

Standards

EN60079-0:2018/IEC60079-0:2017 

(ed.7): 

Explosive 

Atmospheres - Equipment General Requirements. 
EN60079-1:2014/IEC60079-1:2014 

(ed.7): 

Explosive 

Atmospheres - Equipment Protection by Flameproof Enclosures 
“d”. 
EN60079-31:2014/IEC60079-31:2013 

(ed.2): 

Explosive 

Atmospheres - Equipment Dust Ignition Protection by enclosure 
“t”. 

Model No: 

Rating 

BExCBGL2-L2D-
P  

Ex db IIB T6 Gb Ta. -50°C to +55°C  
Ex db IIB T5 Gb Ta. -50°C to +70°C  
Ex tb IIIC T65°C Db Ta. -50°C to +40°C 
Ex tb IIIC T80°C Db Ta. -50°C to +55°C 
Ex tb IIIC T95°C Db Ta. -50°C to +70°C

See Product table for electrical ratings of each unit model 

 

Certificate No.    

KEMA  01ATEX2222X 
IECEx KEM 10.0024 
UL22UKEX2637X 

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

2813 

UKCA Marking and 
Approval Body No. 
 

 

0518 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.  Zones, Gas Group, Category and 

Temperature Classification 

The units can be installed in locations with the following conditions: 
 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation.

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Gas Groupings 

Group IIA

Propane

Group IIB

Ethylene

Group IIC

Hydrogen & Acetylene 

Temperature Classification for Gas Applications

T1

450

o

T2

300

o

C

T3

200

o

C

T4

135

o

C

T5

100ºC

T6

85ºC (up to 55ºC ambient) 

Area Classification Dust 

Zone 21 

Explosive dust air mixture likely to occur in normal 
operation.

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Dust Groupings 

Group IIIA

Combustible Dusts 

Group IIIB

Non-Conductive Dusts 

Group IIIC

Conductive Dusts 

Equipment Category 

2G, 2D

Equipment Protection Level 

Gb, Db,

Maximum Surface Temperature for Dust Applications

65°C at +40°C  

80°C at +55°C  

95°C at +70°C  

Ambient Temperature Range

-50°C to +70°C Gas Groups IIA and IIB and -IIIC 

-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

IP Rating 

IP66/67 to EN/IEC60529 and

IP6X to EN/IEC60079-0, EN/IEC60079-31 

The  unit  must  only  be  installed  by  suitably  qualified  personnel  in 
accordance with the latest issues of the relevant standards: 
  
EN60079-14  /  IEC60079-14:  Explosive  atmospheres  -  Electrical 
installations design, selection and erection 
EN60079-10-1  /  IEC60079-10-1:  Explosive  atmospheres  - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2  /  IEC60079-10-2:  Explosive  atmospheres  - 
Classification of areas. Explosive dust atmospheres 
 
The installation of the unit must also be in accordance with any local 
codes that may apply and should only be carried out by a competent 
electrical engineer who has the necessary training.

 

 

Содержание BExCBL2-L2D-P

Страница 1: ...ent taken by the various units Nominal current at nominal voltage Table 1 Electrical Ratings It is important that a suitable power supply is used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all of the units The above table shows the input current taken by the various units and shows the maximum voltage at which they can be operate...

Страница 2: ...ccur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen Acetylene Temperature Classification for Gas Applications T1 450o C T2 300o C T3 200o C T4 135o C T5 100ºC T6 85ºC up to 55ºC ambient Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust a...

Страница 3: ...d to ensure that the unit cannot move in service Fig 1 Fixing Location for Combined Beacon Beacon 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexagon socket head screws and withdraw the flameproof cover taking extreme care not to damage the flameproof joints in the process M6 cover screws are Class A4 80 stainless steel and only screws of this category can be...

Страница 4: ...n using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the earth conductor under the earth clamp The earth conductor should be at least equal in size and rating to the incoming p...

Страница 5: ...mum resistance value of 3k3Ω and a minimum power rating of 0 5 watts or a minimum resistance value of 500Ω and a minimum power rating of 2 watts The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads should be kept as short as possible Fig 7 End of Line Resistor Placement 13 Flash Rate Settings The BExB2L2D beacons can produce di...

Страница 6: ... Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance The acoustic horn is made out of ABS plastic ther...

Страница 7: ...5W MIN MINIMUM VALUES R1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 3 to ve 24 03 2022 24 03 2022 24 03 2022 BExBGL2D BExC...

Страница 8: ...NTS 1 1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 3 to ve 24 03 2022 24 03 2022 24 03 2022 BExBGL2D BExCBL2 L2D DC LED LE...

Страница 9: ...uality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G Ex db IIB T6 to T4 Gb II 2D Ex tb IIIC T65 C to T130 CDb IP6X Dust Protectionto EN60079 0 EN60079 31 Standards applied EN 60079 0 2012 A11 2013 EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protectionto EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive ...

Страница 10: ...er Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthemarket theequipment conforms with alltechnical andregulatory requirements oftheabovelisteddirectives regulations and standards This Declaration is issued under thesole responsibility ofthemanufacturer...

Страница 11: ... Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIB T6 T4 Gb II 2D Ex tb IIIC T65 C T130 Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2...

Страница 12: ... and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Отзывы: