To set the required output level, adjust the potentiometer on 
the pcb. For maximum output level the potentiometer should 

be set to the fully clockwise position. 
 

15) 

 End of Line Monitoring (DC Units)

 

 

On  BExDCS110-05D  DC  units,  dc  reverse  line  monitoring 
can  be  used  if  required.  All DC  units  have  a  blocking diode 
fitted  in  their  supply  input  lines on  both  the sounder section 

and the beacon section. An end of line monitoring diode or an 
end of  line monitoring  resistor can  be connected  across  the 

+ve  and  –ve  terminals.  If  an  end  of  line  resistor  is  used  it 
must  have  a  minimum  resistance  value  of 3k3  ohms  and  a 

minimum wattage of 0.5 watts or a minimum resistance value 
of 500 ohms and a min.   wattage of 2 watts. If the sounder 

and  beacon  sections  are  wired  to  separate  power  supplies 
then  an  end  of  line  monitoring  component  can  be  used  in 
each section. 

 

16) 

Synchronised Operation

 

 

All  BExDCS110-05D  units  that  are  connected  to  the  same 

supply  line  will  have  a  synchronized  sound  output  and  a 
synchronised flash rate at one flash every second. To ensure 

that the units will be synchronised check that the pin header 
is not fitted, i.e. the two header pins are not shorted together 

(see Figures 4 and 5). 
 

17) 

Flip / Flop Operation

 

 
Two units can be mounted close to each other to form a flip-

flop  operation,  where  the  beacons  will  flash  alternately.  To 
achieve  this  mode  of  operation,  fit  a  pin  header  to  the  flip- 
flop header pins on the electronics board, i.e. the two header 

pins are shorted together, (see figures 4 and 5) on one of the 
two  beacons.  The  first  flash  on  the  beacon  that  has  the 

header fitted will be delayed by ½ second. The two beacons 
will then flash alternately every ½ a second. 

 
 

 
 
 

 
 

 
 

 
 
 

 
 

 
 

 
 

 
 
 

 
 

 

 
 
 
 
 

TONE SELECTION TABLE 

Note Switch No. 6 is not used

 

 

 
 

 
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 

 

Tone Selection 

DIP Switch                                    
Settings 

 
Stage Selection 

Stage 1 

Frequency Description 

1    2   3   4   5 

 

Stage 2 

Stage 3 

Continuous  1000Hz  

Toxic gas alarm 

0    0   0   0   0 

Tone 31 

Tone 11 

Alternating  800/1000Hz  at  0.25s 

intervals 

1    0   0   0   0 

Tone 17 

Tone 5 

Slow  Whoop  500/1200Hz  at  0.3Hz 
with 0.5s gap repeated 

0    1   0   0   0 

Tone 2 

Tone 5 

Sweeping 800/1000 at 1Hz 

1    1   0   0   0 

Tone 6 

Tone 5 

Continuous at 2400Hz 

0    0   1   0   0 

Tone 3 

Tone 27 

Sweeping 2400/2900Hz at 7Hz 

1    0   1   0   0 

Tone 7 

Tone 5 

Sweeping 2400/2900Hz at 1Hz 

0    1   1   0   0 

Tone 10 

Tone 5 

Siren 500/1200/500Hz at 0.3Hz 

1    1   1   0   0 

Tone 2 

Tone 5 

Sawtooth 1200/500Hz at 1Hz 

0    0   0   1   0 

Tone 15 

Tone 2 

10 

Alternating 2400/2900Hz at 2Hz 

1    0   0   1   0 

Tone 7 

Tone 5 

11 

Intermittent  1000Hz  at  0.5Hz 

General alarm

 

0    1   0   1   0 

Tone 31 

Tone 1 

12 

Alternating 800/1000Hz at 0.875Hz 

1    1   0   1   0 

Tone 4 

Tone 5 

13 

Intermittent 2400Hz at 1Hz 

0    0   1   1   0 

Tone 15 

Tone 5 

14 

Intermittent 800Hz 0.25s on 1s off 

1    0   1   1   0 

Tone 4 

Tone 5 

15 

Continuous at 800Hz 

0    1   1   1   0 

Tone 2 

Tone 5 

16 

Intermittent  660Hz  150mS  on, 
150mS off 

1    1   1   1   0 

Tone 18 

Tone 5 

17 

Alternating 544Hz  
(100mS)/440Hz(400mS) 

0    0   0   0   1 

Tone 2 

Tone 27 

18 

Intermittent 660Hz 1.8s on, 1.8s off 

1    0   0   0   1 

Tone 2 

Tone 5 

19 

1400Hz  to  1600Hz  sweep  up  over 
1s - 1600Hz to 1400Hz sweep down  

over 0.5s 

0    1   0   0   1 

Tone 2 

Tone 5 

20 

Continuous 660Hz  

1    1   0   0   1 

Tone 2 

Tone 5 

21 

Alternating 554/440Hz at 1Hz 

0    0   1   0   1 

Tone 2 

Tone 5 

22 

Intermittent 554Hz at 0.875Hz 

1    0   1   0   1 

Tone 2 

Tone 5 

23 

800Hz pulsing at 2Hz 

0    1   1   0   1 

Tone 6 

Tone 5 

24 

Sweeping 800/1000Hz at 50Hz 

1    1   1   0   1 

Tone 29 

Tone 5 

25 

Sweeping 2400/2900Hz at 50Hz 

0    0   0   1   1 

Tone 29 

Tone 5 

26 

Simulated bell sound 

1    0   0   1   1 

Tone 2 

Tone 1 

27 

Continuous 554Hz 

0    1   0   1   1 

Tone 26 

Tone 5 

28 

Continuous 440Hz 

1    1   0   1   1 

Tone 2 

Tone 5 

29 

Sweeping 800/1000Hz at 7Hz 

0    0   1   1   1 

Tone 7 

Tone 5 

30 

420Hz repeating 0.625s on, 0.625s 

off  

Australian alert signal

 

1    0   1   1   1 

Tone 32 

Tone 5 

31 

1200/500Hz at 1 Hz  

Prepare to abandon platform 

0    1   1   1   1 

Tone 11 

Tone 1 

32 

Sweeping 500/1200Hz 3.75s on, 
0.25s off 15Hz 

1    1   1   1   1 

Tone 26 

Tone 1 

Unit No. 2

+

+

-

S2

S3

-

Sounder

PCB

 +   -   

S2

  

S3

Unit No. 1

Beacon 
PCB

 

+   - 

 

+   - 

Beacon 
PCB

Beacon 

PCB

 

+   - 

Sounder

PCB

 +   -   

S2

  

S3

Sounder

PCB

 +   -   

S2

  

S3

Unit No. 3

 

BExDCS110-05D DC Combined Sounder Unit 

Beacon and Sounder Wired for Independent Operation 

NOTE 

Either the +ve or the -ve wire may 
be made common to both the 
sounder and the beacon to reduce 
the number of cores in the cable. 

Содержание BE DCS110-05D Series

Страница 1: ...O NOT OPEN WHEN AN EXPLOSIVE GAS DUST ATMOSPHERE IS PESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C Year of Construction Serial No i...

Страница 2: ...installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check t...

Страница 3: ...glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 I...

Страница 4: ...operate the sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units The operation of the second and third stages is different...

Страница 5: ...ency Description 1 2 3 4 5 Stage 2 Stage 3 1 Continuous 1000Hz Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11 2 Alternating 800 1000Hz at 0 25s intervals 1 0 0 0 0 Tone 17 Tone 5 3 Slow Whoop 500 1200Hz at...

Страница 6: ...r PCB Unit No 1 L N Beacon PCB L N Beacon PCB L N Beacon PCB L N C S2 S3 Sounder PCB L N C S2 S3 Sounder PCB Unit No 3 Unit No 2 C N S3 S2 L Sounder PCB Unit No 1 L N C S2 S3 Beacon PCB L N L N L N Be...

Страница 7: ...ccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d llB T4 ll 2 D Ex tD A21 IPGX T100 C or T115 C Standards applied EN 60079 0...

Отзывы: