sectional areas such as 2.5mm² and above. If the sounder is 
wired  to  the  same  power supply  as  the beacon  always  use 

the flexible interconnecting wires provided. 
 

BEACON SECTION CONNECTIONS 
The cable connections are made into the terminal blocks on 

the  electronic  pcb  assembly  located  in  the  beacon  section 
enclosure. A four-way terminal block is provided on both AC 
and DC beacons. Therefore there are two live terminals and 

two  neutral  terminals  for  the  input  and  output  wiring  on  AC 
units. On the DC units there are two +ve terminals and two -

ve terminals for the input and output wiring. 
 

Wires  having  a  cross  sectional  area  of  up  to  4mm²  can  be 
connected  to  each  terminal  way.  When  connecting  wires  to 
the terminals great care should be taken to dress the wires so 

that  wires  do  not  exert  excess  pressure  on  the  terminal 
blocks. This is particularly important when using cables with 

large cross sectional areas such as 2.5mm² and above. 
 

 
 

 

 

 

13) 

Tone Selection and 2nd and 3rd Stage Alarms

 

 

The BExDCS110-05D sounder section has 32 different tones 

that can be selected for the first stage alarm. The sounders 
can then be switched to sound second and third stage alarm 

tones. The tones are selected by operation of a DIP switch on 
the sounder pcb for both DC and AC units. The tone table on 

page  five  shows  the  switch  positions  for  the  32  tones  and 
which tones are available for the second and third stages. To 

operate the sounder on stage one simply connect the supply 
voltage to the normal supply terminals (+ve and –ve for DC 
units, L and N for AC units).  

The operation of the second and third stages is different for 
DC and AC units. 

 
DC Units Second and Third Stage Tone Selection 

 
The BExDCS110-05D DC sounder section has the facility to 

use  either  +ve  or  –ve  switching  to  change  the  tone  to  the 
second and third stages. For –ve switching connect the two 
headers on the pcb to the left-hand (marked –ve) and centre 

pins. For +ve switching connect the headers to the right hand 
(ve) and the centre pins. To change to the second 

stage tone, connect either a -ve or +ve supply line to terminal 
S2, depending on which switching mode is being used while 

maintaining  the  dc  supply  to  the  +ve  and  –ve  terminals. 
Similarly for the third stage tone, connect a -ve or +ve supply 
line  to  terminal  S3.  The  supply  to  the  S3  terminal  will 

automatically override a supply to the S2 terminal. 
 

AC Units Second and Third Stage Tone Selection 
 

To  select  the  second  and  third  stage  tones  on  the 
BExDCS110-05D  AC  sounder  section,  the  Common  (C) 

terminal  on  the  three  way  terminal  block  on  the  pcb  is 
connected to the S2 terminal for the second stage tone and 
the S3 terminal for the third stage tone. 

 

 

 

 

 

14) 

Volume Control

 

 

The BExDCS110-05D sounder section, with the exception of 
12V DC units, has a volume control to adjust the output level. 

Figure 7 

Figure 6 

BExDCS110-05D  DC Sounder Section 

BExDCS110-05D  AC Sounder Section 

Volume Control 

DIP Switch 

DIP Switch 

Volume Control 

DC Input 
Terminals 

Stage Headers 

Stage Terminals 

AC Input 
Terminals 

 
S2 
S3

 


+

 

       S2 
       S3 
        C 
 
 
        N 
        L

 




N

 

Figure 4 

AC Input 
Terminals 

Interconnecting Terminals to 
sounder pcb (simultaneous 
mode of operation) 

BExDCS110-05D  AC Beacon Section 

Flip / Flop 
Pin Header 

DC Input 

Terminals 

Figure 5 




+

 

Flip / Flop 

Pin Header 

BExDCS110-05D  DC Beacon Section 

Interconnecting Terminals to 
sounder pcb (simultaneous 

mode of operation) 

Содержание BE DCS110-05D Series

Страница 1: ...O NOT OPEN WHEN AN EXPLOSIVE GAS DUST ATMOSPHERE IS PESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C Year of Construction Serial No i...

Страница 2: ...installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check t...

Страница 3: ...glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 I...

Страница 4: ...operate the sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units The operation of the second and third stages is different...

Страница 5: ...ency Description 1 2 3 4 5 Stage 2 Stage 3 1 Continuous 1000Hz Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11 2 Alternating 800 1000Hz at 0 25s intervals 1 0 0 0 0 Tone 17 Tone 5 3 Slow Whoop 500 1200Hz at...

Страница 6: ...r PCB Unit No 1 L N Beacon PCB L N Beacon PCB L N Beacon PCB L N C S2 S3 Sounder PCB L N C S2 S3 Sounder PCB Unit No 3 Unit No 2 C N S3 S2 L Sounder PCB Unit No 1 L N C S2 S3 Beacon PCB L N L N L N Be...

Страница 7: ...ccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d llB T4 ll 2 D Ex tD A21 IPGX T100 C or T115 C Standards applied EN 60079 0...

Отзывы: