European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2463-P      Issue E          19-03-10                               

Sheet 2 of 6 

Area Classification Dust: 

 

Zone 21 

Explosive  dust  air  mixture  likely  to  occur  in 

normal operation. 

Zone 22 

Explosive  dust  air  mixture  not  likely  to  occur, 

and if it does, it will only exist for a short time. 

 
IP Rating: 

IP67 

 

T100ºC Ta < +55ºC 

T115ºC Ta < +70ºC

 

Equipment Category:

 

2G/D 

 
Ambient Temperature Range:

         -50

°

C to +70

°

 

6) 

Location and Mounting

 

 

The  location  of  the  unit  should be  made  with  due  regard  to 
the  area  over  which  both  the  sounder  and  beacon  warning 
signal  must  be  audible  and  visible.  The  unit  should  only  be 

fixed to services that can carry the weight of the unit. 
 

The unit should be securely bolted to a suitable surface using 
the  7mm diameter  boltholes  in  the stainless  steel  U  shaped 

mounting  bracket  (see  figure  1).  The  angle  can  then  be 
adjusted in the direction such that its warning signals can be 

both heard and seen. This can be achieved by loosening the 
two large bracket screws in the side of the unit,  which  allow 
adjustment in steps of 18

°

. On completion of the installation 

the  two  large  bracket  adjustment  screws on  the  side  of  the 
unit  must  be  fully  tightened  to  ensure  that  the  unit  cannot 
move in service. 

 
SAFETY WARNING:  

 

The flashdome guard must not be removed from the unit 

at any time. 

 

 

 

 

7) 

Access to the Flameproof Enclosure

 

 

In order to connect the electrical supply cables to the unit it is 

necessary  to  remove  the  beacon  section  to  gain  access  to 
the flameproof chamber. To achieve this remove the four M6 

hexagon socket head screws (see figure 2) and withdraw the 
beacon  section  taking  extreme  care  not  to  damage  the 

flameproof joints in the process.  
 

Note  the  four 

M6 screws are Class  A4-80 stainless  steel 

and  only  screws of  this  category  can  be used  on  these 
units. 

It  is  therefore  important  that  these  screws  and  their 

spring washers are kept in a safe place during installation. 

On completion of the cable wiring installation the flameproof 
joints should be inspected to ensure that they are clean and 

that  they  have  not  been  damaged  during  installation.  Also 
check  that  the  earth  bonding  wire  between  the  two  casting 

sections  is  secure  and  the  ‘O’  ring  seal  is  in  place.  When 
replacing the beacon section casting, ensure that it is square 

with  the  sounder  section  chamber  casting  before  inserting. 
Carefully push the beacon section in place allowing time for 
the air to be expelled. Only after the beacon section casting is 

fully in place should the four M6 Stainless Steel A4-80 cover  
bolts  and  their  spring  washer  be  inserted  and  tightened 

down.  If  the beacon  section  jams  while  it  is  being  inserted, 
carefully remove it and try again. Never use the cover bolts to 

force the beacon section casting into position. 
 
In case of repair, contact the manufacturer for information on 

the dimensions of the flameproof joints. 
 

 

8) 

Power Supply Selection 

 

It is important that a suitable power supply is used to run the 
unit.  The  power  supply  selected  must  have  the  necessary 

capacity  to  provide  the  input  current  to  all  of  the  units 
connected to the system. The sounder and beacon sections 

can  both  be  wired  to  the  same  power supply  or  to  different 
power supplies 

  
The  following  table  shows  the  input  current  taken  by  the 
sounder section and beacon section of the various units:- 

 

Unit Type 

Input  

 

Sounder   

Max. 

 

 

Voltage   

Current               I/P Volts

 

 
BExDCS110-05D  24V DC   

265mA   

30V 

BExDCS110-05D  12V DC   

195mA   

15V 

BExDCS110-05D  48V DC   

130mA   

58V 

BExDCS110-05D  230V AC   

56mA 

 

264V 

BExDCS110-05D  115V AC   

110mA   

126V 

 

Unit Type 

Input  

 

Beacon   

Max. 

 

 

Voltage   

Current                I/P Volts

 

 
BExDCS110-05D  24V DC   

300mA   

30V 

BExDCS110-05D  12V DC   

750mA   

15V 

BExDCS110-05D  48V DC   

1800mA   

58V 

BExDCS110-05D  230V AC   

55mA 

 

264V 

BExDCS110-05D  115V AC   

140mA   

126V 

 

The above table also shows the maximum voltages at which 

the units can be operated. 

 
Sounder Section 

The input current to the sounder section will vary according to 

the voltage input level and the frequency of the tone selected. 
The  current  levels  shown  above  are  for  the  440Hz 

Continuous tone @ nominal input voltage. The 24V and 48V 

S/S Mounting 
Bracket

 

Sounder 
Section 

Flashdome 
Guard 

Fig 1 

 

Beacon 
Section 

4 off Cover Screws 

External Earth 
Terminal 

Fig 2 

 

Plastic Acoustic Horn 
 (Anti-static Plastic) 
 

Содержание BE DCS110-05D Series

Страница 1: ...O NOT OPEN WHEN AN EXPLOSIVE GAS DUST ATMOSPHERE IS PESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C Year of Construction Serial No i...

Страница 2: ...installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check t...

Страница 3: ...glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 I...

Страница 4: ...operate the sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units The operation of the second and third stages is different...

Страница 5: ...ency Description 1 2 3 4 5 Stage 2 Stage 3 1 Continuous 1000Hz Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11 2 Alternating 800 1000Hz at 0 25s intervals 1 0 0 0 0 Tone 17 Tone 5 3 Slow Whoop 500 1200Hz at...

Страница 6: ...r PCB Unit No 1 L N Beacon PCB L N Beacon PCB L N Beacon PCB L N C S2 S3 Sounder PCB L N C S2 S3 Sounder PCB Unit No 3 Unit No 2 C N S3 S2 L Sounder PCB Unit No 1 L N C S2 S3 Beacon PCB L N L N L N Be...

Страница 7: ...ccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d llB T4 ll 2 D Ex tD A21 IPGX T100 C or T115 C Standards applied EN 60079 0...