background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2463-P      Issue E          19-03-10                               

Sheet 3 of 6 

DC units and the 230V AC, 115V AC units have a switching 
voltage regulator circuit and therefore the input current  level 

will  decrease  slightly  as  the  input  voltage  in  increased  and 
will increase slightly as the input voltage is reduced. The 12V 

units do not have a voltage regulator and therefore their input 
current will increase when the input voltage is increased. 

 
Beacon Section 
The input current to the beacon section will vary according to 

the  voltage  input  level.  The  current  levels shown  above  are 
for  nominal  input  voltage.  The  12V,  24V  and  48V  DC  units 

have a converter circuit and therefore the input current level 
will  decrease  slightly  as  the  input  voltage  in  increased  and 

will increase slightly as the input voltage is reduced.  
 

9) 

 Cable Selection 

 

When selecting the cable size consideration must be given to 
the input current that each unit draws (see table above), the 

number of units on the line and the length of the cable runs. 
The cable size selected must have the necessary capacity to 
provide the input current to  all of the units connected to the 

line.  
 

SAFETY  WARNING:  If  the  unit  is  used  at  high  ambient 
temperatures,  i.e.  over  +40ºC,  then  the  cable  entry 

temperature  may  exceed  +70ºC  and  therefore suitable  heat 
resisting  cables  must  be  used,  with  a  rated  service 
temperature of at least 110ºC. 

 

10) 

  Earthing

 

 

Both AC and DC units must be connected to a good quality 
earth.  The  units  are  provided  with  internal  and  external 
earthing  terminals,  which  are  both,  located  on  the  beacon 

section of the unit (see figures 2 and 3).  
 

 
 

 
 
 

 
 

 
 

 
 

 
 
 

 
 

 
When  using  the  internal  earth  terminal  ensure  that  the 

stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure. 

 
When  using  the  external  earth  terminal  a  cable  crimp  lug 
must be used.  The cable lug should be located between the 

two  M5  stainless  steel  flat  washers.  The  M5  stainless  steel 
spring  washer  must  be fixed between  the  outer  flat  washer 

and the M5 stainless steel nut to ensure that the cable lug is 
secured against loosening and twisting. 

 

The  internal  earth  bonding  wire  ensures  that  a  good quality 
earth is maintained between the sounder section casting and 

the beacon section casting. 
 

11) 

 Cable Glands

 

 

The BExDCS110-05D unit has dual cable gland entries which 
have  an  M20  x  1.5  entry  thread  as  standard.  Only  cable 

glands  approved  for  Ex  ‘d’  applications can  be  used,  which 
must  be suitable  for  the  type  of  cable  being  used  and  also 

meet  the  requirements  of  the  Ex  ‘d’  flameproof  installation 
standard EN60079-14:2008 / IEC60079-14:2007. 
 

When  only  one  cable  entry  is  used  the  other  one  must  be 
closed with an Ex ‘d’ flameproof blanking plug, which must be 

suitably approved for the installation requirements.  
 

For combustible dust applications, the cable entry device and 
blanking  elements  shall  be  in  type  of  explosion  protection 

increased  safety  "e"  or  flameproof  enclosure  "d"  and  shall 
have an IP 6X rating according to EN60529:1992. 
 

SAFETY  WARNING:  If  the  unit  is  used  at  high  ambient 
temperatures,  i.e.  over  +40ºC,  then  the  cable  entry 

temperature  may  exceed  +70ºC  and  therefore suitable  heat 
resisting  cable  glands  must  be  used,  with  a  rated  service 

temperature of at least 110ºC. 
 

12) 

 Cable Connections 

 

The  combined  sounder  beacon  unit  BExDCS110-05D  has 
separate  printed  circuit  boards  in  the  sounder  and  beacon 

sections.  The  terminals  for  the  sounder  are  on  the  printed 
circuit board in the sounder section and the terminals for the 
beacon are on the printed circuit board in the beacon section 

(see figures 4&5 and 6&7). See section 7 of this manual for 
access to the enclosure and the wiring diagrams at the end of 

this manual. 
 

The sounder and beacon sections can be wired to the same 
input supply so that they operate simultaneously or they can 
be wired to separate input supplies so they can be operated 

independently  (see  diagrams  of  pages  5  and  6  of  this 
manual). If the sounder and beacon sections are connected 

to  the  same  input  supply,  the  incoming  cables  should  be 
connected to the input terminals on the beacon board and the 

two connecting wires, that are supplied with the unit, should 
be used to link the supply from the interconnecting terminals 

on  the  beacon  board  down  to  the  supply  terminals  on  the 
sounder board. 
 

SOUNDER SECTION CONECTIONS 
On the AC units a two-way terminal block is provided for the 

live and neutral mains supply wires and a three way terminal 
block is provided for linking the second and third stages, (see 

figure  7).  On  the  DC  units  a  four  way  terminal  block  is 
provided for +ve and –ve supply input and second and third 

stage modes of operation, (see figure 6). 
 
A single wire with a cross sectional area of up to 4mm² can 

be connected to each terminal way or if an input  and output 
wire is required two 2.5mm² wires can be connected to each 

terminal  way.  When  connecting  wires  to  the  terminals  great 
care  should  be  taken  to  dress  the  wire  so  that  when  the 

beacon section is inserted into the chamber the wires do not 
exert  excess  pressure  on  the  terminal  blocks.  This  is 
particularly  important  when  using  cables  with  large  cross 

Internal Bonding Wire Terminal 

 

Internal Earth Terminal 

 

2 off M20  

Cable Entries 

 

Figure 3 

Содержание BE DCS110-05D Series

Страница 1: ...O NOT OPEN WHEN AN EXPLOSIVE GAS DUST ATMOSPHERE IS PESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C Year of Construction Serial No i...

Страница 2: ...installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check t...

Страница 3: ...glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 I...

Страница 4: ...operate the sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units The operation of the second and third stages is different...

Страница 5: ...ency Description 1 2 3 4 5 Stage 2 Stage 3 1 Continuous 1000Hz Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11 2 Alternating 800 1000Hz at 0 25s intervals 1 0 0 0 0 Tone 17 Tone 5 3 Slow Whoop 500 1200Hz at...

Страница 6: ...r PCB Unit No 1 L N Beacon PCB L N Beacon PCB L N Beacon PCB L N C S2 S3 Sounder PCB L N C S2 S3 Sounder PCB Unit No 3 Unit No 2 C N S3 S2 L Sounder PCB Unit No 1 L N C S2 S3 Beacon PCB L N L N L N Be...

Страница 7: ...ccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d llB T4 ll 2 D Ex tD A21 IPGX T100 C or T115 C Standards applied EN 60079 0...

Отзывы: