Environment One Grinder Pump Feature Identification
1. GRINDER PUMP BASIN
– Polyethylene, with fiberglass accessway section (model height 92”
and taller).
2. ACCESSWAY COVER
– Hinged aluminum.
3. ELECTRICAL QUICK DISCONNECT (EQD)
– Cable from pump core terminates here.
4. POWER AND ALARM CABLE
– Circuits to be installed in accordance with local codes.
5. ALARM PANEL
– NEMA 4X enclosure and equipped with circuit breakers. Locate according to
local codes.
6. ALARM DEVICE
– Every installation is to have an alarm device to alert the homeowner of a
potential malfunction. Visual devices should be placed in very conspicuous locations.
7. INLET
– EPDM grommet (4.5” ID). For 4.5” OD DWV pipe (standard).
8. WET WELL VENT
– 2.0” tank vent.
9. GRAVITY SERVICE LINE
– 4” DWV, (4.5 OD). Supplied by others.
9a. STUB-OUT
– 4” X 5’ long
watertight
stub-out, to be installed at time of burial unless the gravity
service line is connected during installation. Supplied by others.
10. DISCHARGE FTG
– 1-1/4” Female NPT, stainless steel.
11. DISCHARGE LINE
– 1-1/4” Nominal pipe size. Supplied by others.
12. CONCRETE ANCHOR
– See Ballast Calculations for specific weight for your station height.
Supplied by others.
13. BEDDING MATERIAL
– 6” minimum depth, round aggregate, (gravel). Supplied by others.
14. FINISHED GRADE
– Grade line to be 1” to 2” below station lid and slope away from the
station.
15. CONDUIT
– 1” or 1-1/4”, material and burial depth as required per national and local codes.
Conduit must enter panel from bottom and be sealed per NEC section 300.5 & 300.7. Supplied by
others.
16. REBAR
– For use with precast concrete ballast. Required to lift tank after ballast (concrete
anchor) has been attached, 4 places, evenly spaced around tank.