9
Operating manual EE23 humidity / temperature sensor
3.4 Display for Model T5
Fig. 4
Display description T5
1. Measurand
2. Units
3. Mesurand selection
SI
US
RH
Relative humidity
%
%
Press the
∆
or
∇
button
to select the measurand
to be displayed.
T
Temperature
°C
°F
h
Enthalpy
kJ/kg
ftlbf/lb
r
Mixture ratio
g/kg
gr/lb
dv
Absolute humidity
g/m³
gr/ft
Tw
Wet-bulb temperature
°C
°F
Td
Dew-point temperature
°C
°F
e
Water vapour partial pressure
mbar
psi
Tab. 1
Mesurand selection
Error description
Error code
(display)
Error
category
Recommended action
Short circuit - on voltage output 1
1)
ERROR: 01
1
Check wiring of outputs
Short circuit - on voltage output 2
1)
Short circuit - on both voltage outputs*
Current loop open - output 1
ERROR: 02
Check wiring of outputs
Current loop open - output 2
Current loop open - both outputs
RH sensor dirty
ERROR: 03
Clean the sensor
2)
Hardware error
ERROR: 05
2
Return the faulty unit for
service
ERROR: 06
ERROR: 08
Temperature measurement failure
ERROR: 07
Humidity measurement failure
ERROR: 09
ERROR: 10
1) not available with 0 - 1 V output
2) see “Cleaning Instructions” at www.epluse.com/ee23
Tab. 2
Description of error messages on the display