Diamond 36kW Manual
Dynatronix, Inc.
198-1600-00 Rev F
Page 39 of 146
and a new cycle is started with one closure of the
operate input contacts. If the contacts are
momentarily closed while a timed cycle is running
the cycle is paused. If the contacts are momentarily
closed (less than one second) while a timed cycle is
paused the cycle will resume. If the contacts are
closed for one second or more while a timed cycle is
paused the cycle is terminated, the next contact
closure will start a new cycle. Note that the operate
state can be changed by the front panel operate
switch or the host port at any time (see
operate switch).
“d.in OPEr CtL” = “on 2”
This configuration works exactly the same as the “on
1” configuration, with the following exception.
After a timed cycle (RTC or ATC) completes the
end of cycle state is cleared with the first closure of
the operate input contacts. The second closure of the
operate input contacts starts a new cycle. Note that
the operate state can be changed by the front panel
operate switch or the host port at any time (see
panel operate switch).
“d.in OPEr CtL” = “on 3”
This configuration works exactly the same as the
“on" configuration, with the following exception.
When the digital input is open operate mode is not
allowed and cannot be overridden by the operate
switch or the host port. As with the other
configurations "standby" commands from the
operate switch or the host port can still be used when
the digital in put is closed. (see
to disable the front panel operate
switch). Additionally the power supply will operate
when it is powered on if the digital input is "closed"
when it is powered on (other configurations require
the digital input to change states from open to close
after the unit is powered on to initiate operate mode).
The digital input configuration can be changed in the “Digital Input System Menu”. Use the
following procedure to configure the digital input. The “System Configuration Menu” is located
within the “Unit Configuration Menu (see
). See
and
A.7.4.2: Digital Input System Menu
for more information regarding menu navigation.
1)
From the “Unit Configuration Menu” rotate the current encoder until the display shows
“CFg” “SyS”, and then press the voltage encoder switch to enter the “System
Configuration Menu”.
2)
From the “System Configuration Menu” rotate the current encoder until the display
shows “SyS” “d.in”, and then press the voltage encoder switch to enter the “Digital Input
Operate Control Configuration Menu”.