Page 3
3101C-TJ101 MANUAL
06/14
MODEL 3101C-TJ101
DELAY EGRESS SYSTEM
WIRING INSTRUCTIONS
705 Emmett Street Bristol, CT 06010
1-877-DynaLock www.dynalock.com
BASIC WIRING
Terminals 1& 2 - Auto-Sensing Power Input. May be 12 or 24 Volts, AC
or DC, uninterrupted. Maximum current draw, by voltage, is as follows:
12V DC: 453mA
12V AC: 1.08A
24V DC: 254mA
24V AC: 750mA
DO NOT INTERRUPT INPUT POWER (TERMINALS 1 & 2) FOR
AUTHORIZED ACCESS/EGRESS. EXTERNAL ACCESS/EGRESS
CONTROLS (EX. KEYPAD, CARD READER, ETC.) SHOULD USE
DEDICATED BYPASS TERMINALS 7 & 8 or 9 & 10 (SEE PAGE 11).
Terminals 3 & 4 - Fire Panel Input. May be normally-open (N.O.) or
normally-closed (N.C.) dry contacts from fire panel (check fire alarm control
jumper “FA” - page 6). DO NOT APPLY POWER TO TERMINALS 3 & 4
OR CIRCUIT BOARD DAMAGE WILL OCCUR.
When the fire panel trips, the 3101C-TJ101 will release, the audible will
sound a constant tone and the bi-color LED (LED1) will change to green.
When the fire panel is reset, the 3101-TJ101 will reset and lock.
Basic hook-up is shown below. For other system features hook-up see “Option Wiring” (page 11).
PROPER OPERATION OF THE 3101C REQUIRES
ADJUSTMENT OF THE EGRESS SENSOR
PROCEED TO EGRESS SENSOR ADJUSTMENT
POWER
FAC
CONTINUOUS
1 2
3 4