Page 9
3101C-TJ101 MANUAL
06/14
MODEL 3101C-TJ101
DELAY EGRESS SYSTEM
WIRING INSTRUCTIONS
705 Emmett Street Bristol, CT 06010
1-877-DynaLock www.dynalock.com
OPTION WIRING
MONITORING OUTPUT DESCRIPTIONS
DELAY EGRESS OUTPUT
Delay egress alarm monitoring.
SPDT dry relay contacts rated 1Amp @ 24 Volts
Contacts change state upon initiation of delayed
egress, after the nuisance delay has elapsed.
They remain in that state until door is closed and
reset.
DYNST OPTION OUTPUT
Dynastat bond sensor monitoring.
SPDT dry relay contacts rated 1Amp @ 24 Volts
Contacts change state to signal lock status as
either secure or unsecure. Armature misalignment
can also create an unsecure condition.
DSM OPTION OUTPUT
Door position sensor monitoring.
SPDT dry relay contacts rated 0.5Amp @ 24 Volts
Contacts change state to signal physical door
position as either closed or open. DSM is an
independent circuit that does not require lock
power to operate.
ATS OPTION OUTPUT
Anti-Tamper Switch monitoring.
SPDT dry relay contacts rated 0.5Amp @ 24 Volts
Contacts change state to signal removal of the
lock electronics cover.
TYPICAL WIRING
NOTE: INDICATORS ARE NOT INCLUDED
NOTE: INDICATORS ARE NOT INCLUDED
NOTE: INDICATORS ARE NOT INCLUDED
NOTE: INDICATORS ARE NOT INCLUDED
13 14 15
ALARM
SECURE
NC C NO
TO INDICATOR
POWER SUPPLY
16 17 18
UNSECURE
SECURE
NC C NO
TO INDICATOR
POWER SUPPLY
19 20 21
OPEN
CLOSED
NC C NO
TO INDICATOR
POWER SUPPLY
22 23 24
TAMPER
NORMAL
NC C NO
TO INDICATOR
POWER SUPPLY
E
F
G
H