Modbus
DYACON UA-1 Manual
UA is a Modbus slave device, the Modbus host must request data from the sensor.
The following describes the Modbus commands and messages. The basic instructions should be
adequate for Modbus host programming. For embedded developers, additional protocol details
are contained in the Modbus Appendix.
The default configuration:
Modbus address
01
Serial Data Parameters 19200, 8-bit data, no parity, 1 stop bit
Supported Functions and Exception Codes
Function
Description
Supported Error and Exception codes*
3
Read Holding Register
0x83: 01, 02, 03, 04
4
Read Input Register
0x84: 01, 02, 03, 04
6
Write Single Register
0x86: 01, 02, 03, 04
16
Write Multiple Registers
0x90: 01, 02, 03, 04
* See Error Code table below for more information.
Sensor Data Requests
Address Register
Access Type
Response
Range
Data Type
Description
201
202
Read
0 to 500*
16-bit Signed Int
Wind speed (m/s)
202
203
Read
0 to 3599*
16-bit Signed Int
Wind direction (°)
203
204
Read
0 to 500
16-bit Signed Int
2 min avg wind speed
204
205
Read
0 to 3599
16-bit Signed Int
2 min avg wind direction
205
206
Read
0 to 500
16-bit Signed Int
10 min avg wind speed
206
207
Read
0 to 3599
16-bit Signed Int
10 min avg wind direction
207
208
Read
0 to 500
16-bit Signed Int
Wind gust speed
208
209
Read
0 to 3599
16-bit Signed Int
Wind gust direction
† See System Status Code section below.
* See Data Format section for numeric conversions.
Page 20/29
Содержание UA-1
Страница 1: ...UA 1 Ultrasonic Anemometer Manual 57 6108 Rev A ...
Страница 2: ...DYACON UA 1 Manual This page intentionally left blank Page 2 29 ...
Страница 4: ...DYACON UA 1 Manual 7 6 Environmental 28 7 7 Accessories 28 8 0 REVISION HISTORY 29 Page 4 29 ...
Страница 13: ...DYACON UA 1 Manual Assembly Instructions Page 13 29 ...
Страница 14: ...Assembly Instructions DYACON UA 1 Manual Page 14 29 ...