Assembly Instructions
DYACON UA-1 Manual
4. Attach cable ties at about 6 in (15 mm) below the wind sensor and every 24 in to 36 in (45
t0 100 mm) along the mast or structure. Route cable to avoid sharp edges or unsupported
horizontal spans.
4.3 Wiring
4.3.1 Wiring Configuration
UA-1 ships with shielded, 4-conductor, outdoor-rated instrumentation cable. The RS-485
(Modbus) connection is a two-wire, half-duplex configuration.
In RS-485 networks, the signal polarity is indicated by a '+' or 'A' and the opposite signal is
indicated by a '-' or 'B'. Some systems use a two-wire configuration and other systems use a
four-wire configuration. Dyacon sensors use a two-wire configuration.
When connecting a Dyacon sensor to a four-wire device, the transmit and receive signals for
each signal polarity are tied together. This means that TX+ and RX+ are tied together on the
host controller as are TX- and RX-.
Page 16/29