20
RMO200D DV-Win Software
Interval
- Interval field allows user to record test results in specific time intervals set in seconds. This
field is unlocked only for Continuous mode of operation. Default interval setting denotes that
measurement will be recorded only once when the test is completed.
OMEGA
- This button performs function of the omega button on RMO instruments, ie. it records last
measurement on click. Omega button is available and visible only in Continuous mode of operation.
Use standard parameters
- If checked, this checkbox allows user to use standard fixed discrete test
parameters previously used in older DV-Win software for RMO devices. If unchecked, user can
manually enter desired test values for Test current and Test duration fields. DV-Win RMO is
designed to automatically set safe test parameters, if user unintentionally inputs non-allowed test
parameter values, so no harm can be done to the RMO device.
7.6 Download
The download tab allows user to transfer recorded measurements from RMO Device to personal computer.
Download is initiated by pressing Start button and it can be stopped at any time by pressing Stop button.
During data transfer progress bar will indicate transfer progress. Measurements can be selectively
downloaded by specifying date, date range, memory positions, current range or by specifying test mode.
7.7 Rmax Settings
Rmax settings are available via Tools - Rmax Settings menu. Rmax function of RMO devices is used to
detect when specific circuit breaker resistance value is reached during measurement. If Rmax value is
detected, RMO device will automatically stop performed test. This function is unchecked by default settings.