19
RMO200D DV-Win Software
DVWin-RMO interface consist of main menu, three tabs (Test info, Test settings, Download), status bar,
toolbar and a table used for displaying results.
7.4 Test info
Test info tab contains fields with information about circuit breaker under test, operator, and environment
conditions. I you are using the instrument for the first time, all fields will be blank and you will need to enter
these information. Once you save the measurement results these information are also saved. Test info tab
will be automatically populated when measurement results from .dwo (internal DV-Win file format) file are
loaded.
Clear All
button on this form will instantly clear all data written in test info fields.
Note: Test info fields don't need to be filled in order to do the testing with RMO devices.
7.5 Test settings
The test settings tab contains test parameters and it is used to start new test or to stop test in progress. This
section briefly describes test parameters functions.
Operation mode:
Single
- selects Single operation mode. Test is performed for fixed period of time. User can only
select desired test current and memory position for test.
Continuous
- selects Contin operation mode. Test is performed for up to 300 seconds. User can
select actual test duration, test current, memory position and interval for this test. Omega button is
available and visible only in this mode after the test is started.
CC
- selects CC (Current Clamp) operation mode. This test allows using Current Clamps for testing.
Test Settings:
Test curent
- this field is used to set the test current. Test current is limited by RMO technical
capabilities. Check your RMO manual for further information.
Test duration
- this field sets the duration of test in seconds. Test duration can be set in Continuous
operation mode only. Single and CC operation modes are performed for fixed amount of time.
Memory position
- determines the memory location where the results of performed test are saved.
Memory position counter is increased automatically after each test. Memory position can also be set
manually by user