background image

23

or Finishing Collar.  Align the tabs on the DVL/

DuraBlack Chimney Adapter with the slots cut into 

the face of the Support Box or Finishing Collar, and 

push it in, and rotate to lock it in place.  Detailed 

instructions for assembling the remainder of the 

close clearance system are included in the DVL 

shipping cartons.

3.  Connection to Oil-Burning Appliance:

  DVL 

is especially  recommended for oil appliances 

because of the corrosive nature of oil-burning 

exhaust.  When connecting to an oil burning 

appliance, refer to National Fire Protection 

Association Standard #211.  Table 6-5.1.1 in NFPA 

211 states that you must allow for 18” clearance 

to combustibles if you are using single wall vent 

connector.  If , however, your appliance is Type-L 

Vent listed and you are using a listed Type-L Vent 

connector, then you are permitted to use the 

clearances as specified by the vent listing.

CHIMNEY  MAINTENANCE 

1.  Creosote and Soot: 

 When wood is burned 

slowly, it produces tar and other organic vapors, 

which combine with expelled moisture to produce 

creosote.  The creosote vapors condense in the 

relatively cool chimney flue of a slow-burning fire.  

As a result, creosote residue accumulates on the 

flue lining.  When ignited, this creosote makes an 

extremely hot fire.  

2.  Access: 

 Chimneys must be installed so that 

access is provided for inspection and cleaning.  

3.  When to Clean: 

 The chimney should be 

inspected at least once every month during the 

heating season to determine if creosote or soot has 

built up.  Check spark arrestor screens at least every 

2 to 4 weeks.  If creosote or soot has accumulated, 

it should be cleaned or replaced to reduce the risk of 

chimney fire.  

4.  How to Clean: 

 Have your chimney cleaned 

by a Certified Chimney Sweep if you have doubts 

about your ability to clean it.  Use a plastic, wood, or 

steel brush.  Do not use a brush that will scratch the 

stainless steel liner of your chimney.  Scrub the spark 

arrestor with a wire brush.  To remove the Chimney 

Cap for cleaning unscrew the four (4) screws that 

attach the cap’s support legs to the cap base.  The 

Tee Cleanout Cap can be removed by turning 

counter-clockwise. Be sure to replace Tee Cleanout 

Cap when you are finished cleaning the chimney.  

5.  Coal: 

 

Warning:

 Coal with a high sulfur content can 

lead to premature failure of the chimney. To reduce 

corrosion in chimneys where coal is burned, clean 

the chimney thoroughly within 48 hours of shutting 

down the stove for the season. An annual inspection is 

required due to the corrosive nature of the fuel. 

6.  Chemical Cleaners: 

 Use chemical cleaners 

only as a last resort, and use only those which 

the manufacturer specifically warrants as being 

noncorrosive to the chimney liner.  DuraVent will 

assume no liability for damage resulting from the use 

of chemical cleaners.  

7.  In Case of Fire: 

 If a flue fire occurs, close all 

appliance air inlets, and call your Fire Department.  

Do not use the chimney again, until it has been 

inspected for possible damage.

8.  Painting: 

 As an option, you can coat all exterior 

metal parts, with the exception of the Chimney 

Cap, with high temperature, rust proof paint.  Wash 

the metal with a vinegar and water solution before 

painting.  Painting the chimney will help to increase 

chimney life.

9.  Creosote Formation: 

 DuraVent assumes 

no liability for any structural damage or roof 

contamination as the result of creosote formation.  It 

is the owner’s responsibility to comply with inspection 

and cleaning requirements as described in these 

instructions, and those of the appliance manufacturer. 

 

Содержание DuraTech Series

Страница 1: ...DuraTech All Fuel Chimney System 5 to 8 diameter Installation Instructions...

Страница 2: ...ep these instructions for future reference This booklet also contains instructions for installing a venting system within an existing masonry chimney and for installations passing through a cathedral...

Страница 3: ...EP DIRECTIONS 6 CEILING SUPPORTED 7 OFFSET ELBOW INSTALLATION 11 EXTENDED ROOF BRACKET INSTALLATION 13 ROOF SUPPORTED INSTALLATIONS 13 TEE SUPPORTED INSTALLATIONS 16 MASONRY FIREPLACE INSTALLATIONS 21...

Страница 4: ...actory built fireplaces check with your fireplace manufacturer Otherwise DuraTech has not been approved for use with solid fuel appliances in Canada DuraTech Chimney is available in 5 6 7 8 diameters...

Страница 5: ...Shield Elbow with swivel Attic Insulation Shield Tee with Tee Cap Elbow Strap Adjustable Tee Support Bracket Adjustable Wall Strap Chimney Cap Anchor Plate Round Ceiling Support Box Extended Roof Bra...

Страница 6: ...mation and enhance draft Include an access door by the Tee Cap for chimney cleaning Refer to Fig 23 STOVE RECOMMENDATIONS Follow the stove manufacturer s instructions The requirements stated below per...

Страница 7: ...d Support Box the Flat Ceiling Support Box the Square Ceiling Support Box Reduced Clearance Support Box or the CAS Ceiling Support The CAS Ceiling Support is only used when installing the CAS system R...

Страница 8: ...pport Box and secure them to the framing members using the 6 1 1 4 long round head wood screws provided see Fig 6 4 Frame Openings Frame openings in each ceiling or floor above the Support Box Fig 7 T...

Страница 9: ...is on the ground floor Support Box is in the 1st floor ceiling you would need a Firestop Radiation Shield at the 2nd floor ceiling and at the 3rd floor ceiling etc including where the chimney penetra...

Страница 10: ...ion Shield until the base sits squarely on the framed opening Fig 7 10 e Secure the Attic Insulation Shield to the top of the framed opening using at least 3 8 penny nails or 3 8 1 1 2 wood screws per...

Страница 11: ...the cap and twist locking it clockwise onto the chimney Do not hold upper portion of the cap and twist as this may damage the cap The Chimney Cap can be removed for chimney cleaning as described in t...

Страница 12: ...8 38 15 36 11 50 15 48 14 61 15 48 6 15 66 15 48 12 17 72 15 48 18 18 78 15 48 24 20 83 30 0 4 15 30 6 6 30 12 9 25 30 18 12 30 30 24 15 35 30 36 21 46 30 48 27 56 30 48 6 29 60 30 48 12 32 65 30 48 1...

Страница 13: ...bottom halves of the Adjustable Leg In order to secure Legs in proper position there is a hole provided in the outer leg where the outer and inner halves overlap Use a 1 4 drill bit to drill through...

Страница 14: ...install the remainder of the Combustible Air System The Support Box must remain level and the top edge of the box must cover the edge of the roof s decking material Square Ceiling Support Boxes are a...

Страница 15: ...im sections into the ceiling Fig 6 4 Complete Installation Refer to Steps 7 9 10 in the Ceiling Supported Installation section to complete the Roof Supported installation Figure 20 Figure 21 2 A Roof...

Страница 16: ...ers Please note that you cannot extend the chimney all the way to the appliance you must have some connector pipe 1 Cut and frame opening to provide a minimum of 2 clearance on all sides of the chimne...

Страница 17: ...uter walls at this location Refer to Table 2 for the appropriate framing dimensions 3 Install Wall Thimble The Wall Thimble is two piece component which includes the Interior half and the Exterior hal...

Страница 18: ...ust for desired clearance to wall and secure by tightening bolts Figs 26 27 5 Install Tee and Cleanout Chimney Figure 25 Figure 26 INSTALLATION WITH TEE BELOW TEE SUPPORT SHOWN WITH LEG BRACKETS MOUNT...

Страница 19: ...on to the female end of the Chimney Branch by twisting clockwise 8 Complete Chimney Attach the Chimney Sections as in Step 7 in the Ceiling Supported Installation section Secure the chimney to the wa...

Страница 20: ...e the Chase Top Flashing Spacers to allow the proper air gap clearances on the galvanized sheet The Chase Top Flashing Spacers are available to insure that the proper air gap is maintained Figure 29 d...

Страница 21: ...th a high temperature 1000 F sealant Secure Anchor Plate with at least 4 1 4 x 4 masonry anchors Fig 30 It is very important that the Anchor Plate is level Be sure to maintain a 1 min clearance to com...

Страница 22: ...he Slip Connector or Snap LockAdapter slips into the opening in the Ceiling Support or Finishing Collar Align the tabs on the Slip Connector or Snap LockAdapter with the notches in the face of the Sup...

Страница 23: ...sk of chimney fire 4 How to Clean Have your chimney cleaned by a Certified Chimney Sweep if you have doubts about your ability to clean it Use a plastic wood or steel brush Do not use a brush that wil...

Страница 24: ...Sweep orVENTINOX installer The Liner and Components warranty is further subject to compliance with the following requirements throughout the warranty period The chimney must have a chimney cap and che...

Отзывы: