background image

8

 

S

UBMITTAL

 

R

ECORD

 

FOR

 

D

URA

S

TACK

 

M

ODELS

 

DCL,

 

DAS1,

 

DIS1,

 

DIS2

 

AND

 

DIS4

 

M&G

 

D

URA

V

ENT

 

|

 

10

 

J

UPITER

 

L

ANE

 

|

 

A

LBANY

,

 

N

EW

 

Y

ORK

 

www.duravent.com

 

 

VARIABLE LENGTH (LV)

 

 

The Variable  Length  (

LV

) has one major  function.  It makes  up odd lengths 

of duct. It must not be used for expansion compensation.

 

 

It is shipped with  a flanged retaining band assembly on the inner sliding wall.  
The 

LV

 is adjustable from 7 1/2 to 28 inch.  

See Figure  1 6 . 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 16 – Variable Length (LV) 

 

 

TEES

 

 

90

° 

TEE (T90)

 

 

The 90° Tee is generally used to connect horizontal connectors into a vertical 
section as well as a drain or inspection fittings. 
 

NOTE

: For the  maximum height of  chimney above  a based  supported Tee, see Table  4 

in the SUPPORT METHODS AND HEIGHT LIMITS section.

 

 

 

                  

 

Figure 17 – T90 

TEE PRECAUTION

 

 

1. Use an adjustable  length in all horizontal  breechings  or laterals.

 

2. If more than ¼”  of thermal expansion is expected between the 

tee and the next fixed support point;

 

a. The tee should be protected from  bending moments  by use of an Adjustable

 

Length (See the section on the Adjustable Length)

 

b.     And the use of two axis support is recommended.

 

3. Provide access for easy removal of Tee Caps.

 

 
 

45 TEE (T45) and DOUBLE 45 TEE (TD45)

 

 
See Figure 18 for the 45 Tee (T45) and Figure 19 for the Double Tee 
(DT45) 
Isolate these Tees from the effectives of Thermal Expansion. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Top Figure 18 T45 | Bottom | Figure 19 |Double Tee 45 (DT45) 

 

LATERAL TEE (BT)

 

 

The Lateral Tee (BT) is a 45 Tee with a 45 Elbow integrated in it. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 20 Lateral Tee (BT) 

 
 
 
 
 
 

 

Half

 

Outer

 

Retaining

 

Band

 

Flow

 

Gas

 

Flow

Cuttable

 

half

 

siding

  

outer

 

casing

 

Adjustable

 

Flanged

 

retaining

 

Band

 

Cuttable

 

sliding

 

Inner

 

Wall

 

Содержание DAS1 22 E30 CE

Страница 1: ...INSULATED DIS1 1 INCH CERAMIC FIBER INSULATED DIS2 2 INCH CERAMIC FIBER INSULATED DIS4 4 INCH CERAMIC FIBER INSULATED DCL SINGLE WALL MATERIAL SELECTION FLUE INNER WALL CASING OUTER WALL 304 304 316...

Страница 2: ...tent service at temperatures not exceeding 1800 F As such Model DAS PRO and D I S PRO Models are suitable for use with ovens and furnaces as described in the Chimney Selection Chart of NFPA No 211 in...

Страница 3: ...d ceiling or floor above the hood through any concealed spaces to or through the roof to maintain the integrity of the fire separations required by the applicable building code provisions If the build...

Страница 4: ...re used to anchor a chimney against upward downward and angular displacement 2 These supports and guides used with thermal expansion devices prevent bending stresses on the chimney elbows and joints 3...

Страница 5: ...23 19 16 12 14 to 24 19 19 16 14 10 26 to 36 15 15 13 11 8 Dimensions are in inches diameter and feet distance EXTERIOR CORROSION PROTECTION It is recommended to apply an exterior grade high heat pain...

Страница 6: ...F S 2000 is water soluble and should not be used where exposed to weather Part No S 375 Nuflex 302 General Purpose is a low temperature grey silicone 450 F only for weathering sealing on outdoor seams...

Страница 7: ...band when assembled Figure 10 Joint Assembly Step 5 STEP 6 Secure the Outer Casing Band with the Outer Band BSE Joint installation is now completed NOTE For exterior installations it is recommended t...

Страница 8: ...not designed to withstand bending moment forces Because the amount of outer casing axial movement is the same as inner casing movement the outer jackets of piping must slide to avoid excessive forces...

Страница 9: ...IGHT LIMITS section Figure 17 T90 TEE PRECAUTION 1 Use an adjustable length in all horizontal breechings or laterals 2 If more than of thermal expansion is expected between the tee and the next fixed...

Страница 10: ...ly as described in JOINT ASSEMBLY section Elbows are used in combination to make different angles ranging from 3 to 90 in horizontal and vertical segments of the duct system ELBOW 3 degree E3 Figure 2...

Страница 11: ...8 11 7 8 32 1 4 26 3 8 2 5 8 6 7 8 12 1 2 34 1 4 28 3 8 2 3 4 7 1 8 13 36 1 4 30 3 8 2 3 4 7 3 8 13 5 8 38 1 4 32 3 8 2 7 8 7 5 8 14 1 8 40 1 4 34 3 8 3 8 14 3 4 42 1 4 36 3 8 3 8 1 4 15 3 8 44 1 4 D...

Страница 12: ...ow DIS4 Diameter in 3 15 30 45 90 5 1 2 2 3 4 6 1 8 10 24 1 2 6 1 2 2 3 4 6 1 4 10 1 4 25 1 2 7 1 2 2 3 4 6 3 8 10 1 2 26 1 2 8 1 2 2 3 4 6 1 2 10 7 8 27 1 2 9 1 2 2 7 8 6 5 8 11 1 8 28 1 2 10 1 2 2 7...

Страница 13: ...imum support the entire perimeter of the Plate Support must be attached to structural framing WARNING RISK OF FIRE DO NOT ATTACH THE PLATE SUPPORT TO COMBUSTIBLE CONSTRUCTION HEAVY DUTY WALL SUPPORT W...

Страница 14: ...D HEAVY DUTY FLOOR GUIDE FGHD A Heavy Duty Floor Guide is similar in function to a Heavy Duty Wall Guide or Full Angle Ring but has been modified for use at floor penetrations The angle brackets and s...

Страница 15: ...ration It can be supported by bracing with a Half Angle Ring HAR an Anchor Plate AP or an Anchor Plate Length APL SECTION F ROOF PENETRATION and FLASHINGS Flashing F The flat Roof Flashing F is used i...

Страница 16: ...xhaust system backfire Engines have the potential to inject unburned fuel into an exhaust system during start up or due to an engine malfunction This unburned fuel creates a condition where a backfire...

Отзывы: