![DURAG D-FL 200 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/durag/d-fl-200/d-fl-200_owners-manual_2541136023.webp)
D-FL 200 / Rev. 6
20
______________________________________________________________________________________________________
Industrie Elektronik GmbH & Co KG
R12
zero_tmperature_in
Beginning of measuring range for temperature sensor (4
mA) (0-800°C) (corr. to 32-1472°F)
R13
span_tmperature_in
End of measuring range for temperature sensor (20 mA) (0-
800°C) (corr. to 32-1472°F)
R14
zero_pressure_in
Beginning of measuring range for absolute pressure sensor
(4 mA) (0-1500hPa)
R15
span_pressure_in
End of measuring range for absolute pressure sensor (20
mA) (0-1500hPa)
R16
const_tmp
constant temperature (0-800°C) (corr. to 32-1472°F)
R17
const_p
constant absolute pressure (0-1500hPa),
default 1013
Parameter code_2
Release code for internal parameterisation,
only for internal
use at Durag factory, code = 200
R22
frequency
Drive frequency for ultrasonic sensor / evaluation algorithm
(10-100kHz),
MK1=50kHz, MK2=41kHz, MK3=30kHz
R23 amplitude
min.
Minimum signal amplitude, values below this limit are not
evaluated. If this appears 30 seconds in a row, the error
detection is launched (E16-E19),
(0-2000), default 350
R24
amplifier target
Set point for the automatic gain control,
constant 1900
R25
amplification f..
Amplification factor/ manual/ automatic; values
between 1 and 512 will set the variable amplifier to a fixed
amplification, values greater than 512 enable the automatic
gain control (0-1000),
default 600
R26
assessment level
Assessment level, used for searching of the trigger point,
constant 10
input temperature
mA input for temperature
input pressure
mA input for absolute pressure
R27
error detection
Error detection system, enabled=1, disabled=0; single error
evaluations can be disabled by setting the value or the sum
of values: 2
Æ
E12-E15; 4
Æ
E16-E19; 8
Æ
E20-E23; 16
Æ
E24-
E27; 32
Æ
E28-E31; 64
Æ
E32-E33
R28
zero suppress
Zero suppress of gas flow velocity (0-3m/s) (10ft)
R29
sensor offset
Sensor offset , (0-600mm) (corr. to 23,6in),
default 0
R30
noise limit
noise limit, signals with a higher noise component are not
evaluated. If this appears longer than 30 seconds in a row,
the error detection is launched (E24-E27) (0-2000), default
450
R31
ultras. speed NT
Ultrasonic speed at 0°C (100-500m/s),