D-FL 200 / Rev. 6
19
______________________________________________________________________________________________________
Industrie Elektronik GmbH & Co KG
Parameter
Code 1
Store release code for parameterisation with
‘STO-Key’ code = 100
R01
integration time
Integration time (1-180s)
R02
limit value
Limit value 1,in relation to the standard volumetric flow (1-
9999x10
3
Nm
3
/h ) (1Nm
3
/h =35,3Nft
3
/h)
R03
measuring path
Measuring path length (0-30m) (1m=3,28ft)
R04 angle
Angle of installation (0°-80°)
R05 cross-section
Stack cross section (0-99,99m²) (1m²=10,76ft²)
R06 corct-factor
Correction factor (0-5) default 1
R07 offset
Zero point offset (-2m/s…+2m/s) default 0
R08
span mA .out1
Measuring range end value of the mA output for
the standard volumetric flow measurement
(1-99,99x10
3
Nm³/h)
R09
span mA .out2
Measuring range end value of the mA output for
the gas velocity measurement (0-99,99 m/s)
R10 measuring
plane
1 Measuring plane 0001
2 Measuring planes 0002
corresponds with two
transducers (standard)
corresponds with four
transducers
R11
calculation mode
Calculation
mode
Calculation
0000
0001
0002
0003
0004
0005
0006
constant temperature,
constant absolute pressure
extern temperature input,
constant absolute pressure
constant temperature,
extern absolute pressure input
extern temperature input and
extern absolute pressure input
ultrasonic temperature calculation
and constant absolute pressure
ultrasonic temperature calculation
and extern absolute pressure input
ultrasonic temperature calculation
and constant absolute pressure, output of
the ultrasonic temperature on standard flow
output, measuring range 0-400°C (corr. 32-
752°F)