background image

 

 

 

 

Page 6 of 47 

DuraComm Annunciator Internal Operation Basics 

The Full Test Point Voltage for the DuraComm Annunciator is reduced by the internal current limiter for 

each circuit (10ma for each channel CH1 to CH6). The voltage drop is minimal for a normal state, trouble 

alarm, open circuit fault, or test point short to GND1. If the test point positive wire is shorted to GND1, 

the current limiter drops all the Vs voltage across itself, and limits the current to 10ma to protect Vs.  

For CH1 to CH6 the internal Vs is 12VDC, and the Test Point Positive voltage is approximately 11.5 VDC 

for normal operation, and the measured test point voltage is approximately 5.7 VDC. 

Vs is 5 VDC for CH7 (Antenna). CH7 uses approximately 50 Ohms for R1 and EOL, so that it can detect 

faults and trouble through the 50 Ohm Coax to the antenna, using two bias tees and a 50 Ohm load. See 

Figure x for circuit. The internal 5 VDC current limiter is 100ma. This channel can be used to monitor a 

relay, but it still requires the 50 Ohm EOL. 

The 12 VDC and 5 VDC supplies are isolated from each other and from earth ground. A single short to 

earth ground  doesn’t cause any faults because it will not interfere with any trouble alarms.  

The Audible alarm automatically sounds at the same rate as the flashing RED or Blue LEDs (about once 

per /-). The audible alarm is automatically cancelled  when no alarms or faults are active. The 

Audible alarm can be manually muted or unmuted by a button located inside the annunciator door for 

security. The audible alarm cannot be “muted” unless there is an active alarm or fault. 

A self-test button is also located inside the door of the annunciator. An inspector should be prepared to 

note that channels 1 thru 7 should cycle BLUE flashing, to GREEN solid, to RED flashing, then back to the 

current system status. When the button is pressed, the outside managed wires are temporarily 

disconnected, and internal hardware simulates a short to internal common to simulate a Fault (BLUE 

LEDs), , a normal EOL condition (GREEN LEDs), and an alarm (short across managed lines – RED lights). 

The front panel lights will cycle thru the colors for these conditions, and the FormC relays that connect 

to the Fire Alarm Panel will cycle thru the proper states. 

(NOTE: This will generate alarms at the Fire 

Alarm Panel. – Notify the responsible monitoring parties before preforming a test.)

 The RED lights for 

alarms and the BLUE lights for faults will flash approximately once per second when they are active. The 

green lights (Normal) do not flash. The self test  Once the self-test completes it will re-connect to the 

managed wires and show the current status of the wires. 

DuraComm Annunciator Remote Monitoring Features 

Monitor test point voltages and alarm levels for managed connections with bar graph display. 

Monitor internal annunciator back-up battery voltage. Set alarm level and notifications. 

Set user access  

View alarm, fault, and normal status for all managed connections to BDA equipment. 

Configure device and network settings 

Содержание PSDA-MU1

Страница 1: ...nitoring via Ethernet This allows the test point voltages to be monitored in relation to their alarm points by a bar graph for each monitored input The internal battery backup voltage is also monitore...

Страница 2: ...on 11 Supervised Form C Contacts from Equipment 12 Fire Alarm Panel Connections 15 Section 3 Self Test 16 Section 4 Remote Monitoring Configuration and Operation 18 SITEGUARD Description 18 Prerequisi...

Страница 3: ...screen Notes 41 Battery 41 Section 6 Internal Information 42 Annunciator Board Internal Connector Layout 42 Annunciator Board Jumper Options Only Change for Non Standard Installation 44 Annunciator B...

Страница 4: ...9 Audible Alarm with internal Mute and Unmute buttons and programmable scheduled Unmute Audible Alarm Disable Internet Browser Viewable Status Page Configurable eMail Notifications and SNMP Alarms wit...

Страница 5: ...R2 R1 R2 or Vs 2 This produces a GREEN LED A trouble alarm switch closure will short out the EOL resistor and the full Vs voltage will be applied to the test point across R1 only so the test point vol...

Страница 6: ...ble alarm can be manually muted or unmuted by a button located inside the annunciator door for security The audible alarm cannot be muted unless there is an active alarm or fault A self test button is...

Страница 7: ...trolled independently The Antenna channel is set at about 2 Volts Fault alarm levels Blue lights are set to a common value by digital to analog converter output 1 on the RMCU board and this can also b...

Страница 8: ...structions for PSDA MU1Annunciator 2 CAUTION Danger of explosion if battery is incorrectly replaced Replace only with the same type recommended by the manufacturer Dispose of used battery according to...

Страница 9: ...d 5V regulated supplies Annunciator Board Battery Remote Monitoring and Control Board Mute Cancel Mute Self Test Battery Charger Under Battery Breaker Ethernet Fire Alarm Panel Connections BDA Connect...

Страница 10: ...er AC Input Cord with Wago Connectors Frame Ground Post on Right Side Bottom Figure 3 Mounting Holes and AC Installation Holes to mount the annunciator are located at the rear four corners of the box...

Страница 11: ...Internet BDA wiring and fire alarm panel cables through separate UL Type 4X Waterproof Conduit Hubs Two Wago connectors are provided on the Internal battery charger power cord for Line and Neutral co...

Страница 12: ...m Trouble To Fire Alarm Panel J109 CH1 CH7 Monitored Lines to BDA J700_CH1 EOL Resistor Mount J700_CH2 EOL Resistor Mount J700_CH3 EOL Resistor Mount J700_CH4 EOL Resistor Mount J700_CH5 EOL Resistor...

Страница 13: ...ed light Multiple ground faults across multiple channels could cause unpredictable results If for some strange reason the test point supply or test point are shorted to the internal ground it will sho...

Страница 14: ...CH3 CH3 EOL 10 Kohm Alarm2 CH4 CH4 EOL 10 Kohm Alarm2 CH5 CH5 EOL 10 Kohm Alarm2 CH6 CH6 EOL 10 Kohm Alarm2 Transmitter CH7 CH7 Earth 10 ma 10 ma 10 ma 10 ma 10 ma 10 ma 12VDC G1 100 ma 5VDC G2 Curre...

Страница 15: ...NC COM NO NC COM NO NC R EOL J700_CH1 R EOL J700_CH2 J700_CH3 R EOL J108 CH 7 S F S T COM NO NC COM NO NC COM NO NC R EOL J1100 R EOL J400_F J400_T R EOL Fire Alarm Panel EOL Resistors Channel 1 Name...

Страница 16: ...nnunciator board if it is not needed Zip tie this to the cable harness to prevent it from contacting other exposed pins inside the PSDA MU1when not connected Power Up The PSDA MU To power up the PSDA...

Страница 17: ...point common a normal condition internal EOL substitution and an alarm short across monitored pair All channels will cycle at the same time Assuming all channels are GREEN to begin with LEDs will cha...

Страница 18: ...factory settings do not perform correctly in your installation Other changes may cause unpredictable or unsafe operation Internet Networking Addresses Usernames and Passwords Device Name Date Time and...

Страница 19: ...IP Scanner In Angry IP Scanner you should add the MAC address Fetcher under Tools Fetchers The DuraComm MAC addresses all start with a base address of 70 B3 D5 6B 3 Write down the IP address of the SI...

Страница 20: ...e final network settings for the SITEGUARD Open a Web Connection to the SITEGUARD Use your favorite device and browser Chrome Firefox internet Explorer etc and enter the IP address of the power supply...

Страница 21: ...r the user name and password Factory default usernames and passwords are as follows Admin Users have full control of the device Username admin Password admin Control users have limited control capabil...

Страница 22: ...Page 22 of 47 NETWORK SETUP...

Страница 23: ...e SITEGUARD When the MIB file has been loaded complete the SNMP Setup section on the Network Setup page of the SITEGUARD to configure it for use with your monitoring solution User specific authenticat...

Страница 24: ...may be needed if you have difficulty setting up your SSL mail connection as with Gmail There may additional requirements since email security changes rapidly To send periodic Heartbeat emails to get s...

Страница 25: ...Page 25 of 47 DEVICE SETUP...

Страница 26: ...Log Alarms Yes You can log alarms log periodically by setting the Logging Rate minutes log both or log none by choosing Log Alarms No and setting the Logging Rate to 0 The Alarm log entry is identifie...

Страница 27: ...Page 27 of 47 SENSOR SETUP...

Страница 28: ...Page 28 of 47 Sensor Setup continued DAC and Scheduling...

Страница 29: ...test timing so use this sparingly when configuring your system Digital Outputs are factory configured for integrated operation with the annunciator board and must not be changed Analog and digital ala...

Страница 30: ...Page 30 of 47 ALARM SETUP ANALOG CHANNELS...

Страница 31: ...Page 31 of 47 ALARM SETUP TEMPERATURE...

Страница 32: ...Page 32 of 47 ALARM SETUP DIGITAL CHANNELS...

Страница 33: ...Page 33 of 47 ALARM SETUP SCHEDULING...

Страница 34: ...set This is accomplished by selecting the custom name of the channel in the dropdown box next to the Analogs label For example we are looking at the settings for the Amp Meter 1 channel in the screen...

Страница 35: ...Internal Battery Voltage Volts 14 5 15 10 10 5 Digital alarms for inputs and outputs as well as the email notifications for them are also configured in this screen Digital input alarm conditions can...

Страница 36: ...Page 36 of 47 USER SETUP...

Страница 37: ...on this page To enable SNMPV3 see the Device Setup page NOTE To hard reset your device back to factory network settings press the red button on the SITEGUARD PCB and hold it for more than 20 seconds...

Страница 38: ...TE MONITORING AND CONTROL STATUS PAGE Status screen This screen shows the status of all analog and digital inputs as well as analog and digital outputs A user can also download the Log file from this...

Страница 39: ...Page 39 of 47 CHARTS SCREEN DEFAULT ARCHIVE DATA...

Страница 40: ...Page 40 of 47 CHARTS SCREEN LIVE DATA...

Страница 41: ...e Goto Live button for each channel will show data samples at the fastest rate approximately 0 5 second and the live data always grows from the left with the chart data shifting left when the chart is...

Страница 42: ...nnector Layout J103 To SiteGraph J104 To Annunciator Power Supply J600 Self Test LED For External LED J300 Mute LED For External LED J102 SelfTest Start J101 Mute J111 Cancel Mute J110 Sonalert Connec...

Страница 43: ...nnel 2 Test Point Channel 3 Test Point Channel 4 Test Point Channel 5 Test Point Channel 6 Test Point Channel 7 Test Point Channel 1 Trouble Control Channel 2 Trouble Control Channel 3 Trouble Control...

Страница 44: ...y Change for Non Standard Installation J400_T System Trouble LED Color J100 System Fault System Trouble Enable Disable P300 Audible Alarm Enable Dis En DO Not Remove Jumper Default Configuration Shown...

Страница 45: ...age 45 of 47 Annunciator Board Test Points and LEDs TP102 Audible Alarm Enable Referenced to GND at TP100 TP101 5V GND2 Quick Connect Blue LED SelfTest Figure 11 Annunciator Board LEDs and Test Points...

Страница 46: ...s 10 W x 12 H x 6 5 D Shipping Weight 12 lbs Battery MK Battery ES7 12 T2 Network Connector RJ 45 10 100 Ethernet with activity LEDs Backup Battery for Real Time Clock CR2032 Memory Card Micro SD Alar...

Страница 47: ...prior to inclusion of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of pur...

Отзывы: