Contatto
MCP 4 – User's manual
DUEMMEGI
1- MAIN FEATURES
1.1- Required Hardware and Software tools
To use
MCP 4
, the software tools MCP IDE is required, running on a PC (WXP, W7, W8). Minimum
hardware required: 1000 MHz processor and 512 Mbytes minimum RAM.
MCP IDE software tools also provides MCP Visio program, allowing to display in a graphical way the status of
the field and all parameters of MCP 4, and other programs allowing specific function.
1.2- Main features of MCP 4
2032 virtual digital points
1024 16-bit registers
1024 16-bit counters
512 16-bit timers
127 real input addresses up to 4-channel 16-bit each one
127 real output addresses up to 4-channel 16-bit each one
Special virtual points:
V2032
: when set to 1, MCP 4 suspends the equations calculation and the execution of the scripts;
when reset to 0, the activity of MCP 4 restarts normally. The point V2032 will be however
automatically reset to 0 after a timeout
V2020
÷
V2027
: it becomes active in case of communication failure for more than 10 seconds on
the relative socket 1 ÷ 8 of the ETH port
V2019
: the activation of this point causes the reset and the re-initialization of Ethernet interface
V2018
: activated when a communication loss on COM4 (RS485) occurs for more than 5 seconds
V2017
: activated when one or more MODBUS slaves do not answer to MCP 4 (set in MODBUS
master mode) for more than 50 retries; it will be deactivated after a full polling cycle to slave
devices without errors
V2016
: activated when the communication with WEBS fails
V2015
: reserved, new data are present in the NOTIFY buffer
V2014
: activated during times from sunrise to sunset
V2013
: reserved
V2012
: activated when a communication loss on COM2 (RS485) occurs for more than 5 seconds
V2011
: activated when a communication loss on COM1 (RS232) occurs for more than 5 seconds
V2010
: activated 0.5 seconds after the end of initialization procedure
V2009
: the buffer of analog event (LOG or LOGC) is full or old events have been overwritten
V2008
: the buffer of binary event (EVENT or EVENTC) is full or old events have been overwritten
V2007
: reserved
V2006
: reserved
V2005
: error during the execution of a script (e.g. not valid instruction)
V2004
: timeout during the execution of a script (>500msec)
V2003
: 1sec period clock (toggle its status every 0.5 seconds)
V2002
: bus failure
V2001
: module failure
Page 6 of 87
Rel.: 1.2 October 2018
DUEMMEGI