Notice NT 06
D.T.S. - ZI Parc d’Activités de la Gare - BP N° 27 - 77831 OZOIR LA FERRIÉRE CEDEX – France
Rev. 7
33(0)1 64 40 27 26 - Fax (33.0)1 64 40 20 11 -
www.dtselec.fr
du 19/10/2011
Performance SATI
MOUNTING AND MAINTENANCE INSTRUCTIONS NT 06
SELF-CONTAINED EMERGENCY LIGHTING
FLAMEPROOF Ex d – Ex de IIC T6 Gb - IP 66
AUTOMATIC TEST SYSTEMS- XEL 80A AK AI VA VAK VAI - XEL300A AK AI VA VAK VAI
ADRESSABLE - XEL 80 SI VSI - XEL 300 SI VSI
Versions AI, SI, VAI et VSI
Versions A, AK, VA et VAK
I- SPECIFICATIONS
Protection class
: I
Duration :
1
hour
Control
: remote control
Optical equipment
: glass (indication V) or polycarbonate; « V » indication means glass protection tube
(ex. XEL 80 VAK)
Certification code
:
Ex d IIC T6 Gb – Ex de IIC T6 Gb
:
Ex tb IIIC T80°C Db IP66 / ou Ex tD A21 T80°C IP6x (model AI ou SI).
Operating zones
: Gas ; zones 1+2 / Dust ; zones 21+22
Power supply
: 230V 50Hz
SPECIAL CONDITION FOR SAFE USE;
The width of flameproof joints is more than the values specified in tables 3 and 4 of the standard EN 60079-1.
- During the installation, the user will take into consideration that the equipment underwent only a shock corresponding to energy of a low risk.
- Against the risk from electrostatic discharge, clean the transparent tube with a damp cloth. Do not use agressive liquid to clean the
polycarbonate tube.
Lumen FLUX
GAS
DUST
TYPE NF
Licence
N°
WEIGHT
(in Kg)
IP/IK
After
5 mn
After 1
hour
T° Class
Tamb
≤
+ 55 °C
Time delay
before
opening
T° dust
Tamb = + 40°C
Time delay
before
opening
XEL-80A T
06034 4.7
XEL-80AK T
06035
4.7
XEL-80AI
T 06036
5.5
XEL-80SI T
06033 5.5
66/08
XEL-80VA T
06045
6.5
XEL-80VAK T
06046
6.5
XEL-80VAI T
06047
7.3
XEL-80VSI T
06048
7.3
66/04
80
70
T6
30 mn
T80°C
30 mn
XEL-300A T
06038
5
XEL-300AK T
06039
5
XEL-300AI T
06040
5.5
XEL-300SI T
06037
5.5
66/08
XEL-300VA T
06049
7
XEL-300VAK T
06050
7
XEL-300VAI T
06051
7.5
XEL-300VSI T
06052
7.5
66/04
300 280
T6 - T80°C -
240
Cable gland ¾ NPT
Plug ¾ NPT
Cable gland M20