Controls and Indications
43
Icon
Description
Test Mode
This button places the module into its Test Mode
.
Once in Test Mode
,
the
module responds to the Start
button to send a start request to the DSE8x10
module over the MSC Link. The module monitors the MSC Link for feedback from
the DSE8x10 module to confirm the generator bus is available.
Once the generator bus is available, it is automatically placed on load (‘Close
Bus’ becomes active), synchronising to the Mains if required. Depending upon
module configuration, the generator bus remains in constant parallel with the
Mains or proceeds to run in island operation (‘Close Mains’ becomes inactive).
The generator bus remains on load until either the Stop/Reset Mode
or
Auto Mode
is selected.